RECLOSER CONTROL EVRC2A-N6,NT
http://www.entecene.co.kr
122
EN
HANCED
TEC
HNOLOGY
7.1. Reclose (79)
After a fault has occurred, the Reclose element closes the recloser when the programmed reclose
interval time expires. The number of operation lockout setting is programmed one to five, and
each reclose shot has its own separate reclose interval timer.
If the fault is permanent and the recloser continues to trip and reclose, the Reclose element will
continue to increment the operating counter. If this continues to the maximum number of the
operating lockout programmed in the Reclose element, the reclose logic lockouts.
If the fault is transient, then the reclose logic is reset by the reset logic.
The reclosing element can be disabled in the Primary, Alternate settings by one operating lockout
or by
[RECLOSE ENABLED]
push button on user interface panel.
The Reclose Element should be enabled to the following settings.
PRIMARY SETTING / PROTECTION / OPERATIONS / Lockout-PHA
Range
1 ~ 5
Default
4
Step
1
Select the total number of the phase trip operations.
This setting is used to change the total number of the phase trip
operations.
PRIMARY SETTING / PROTECTION / OPERATIONS / Lockout-GND
Range
1 ~ 5
Default
4
Step
1
Select the total number of the ground trip operations.
This setting is used to change the total number of the ground trip
operations.
PRIMARY SETTING / PROTECTION / OPERATIONS / Lockout-SEF
Range
1 ~ 5
Default
4
Step
1
Select the total number of the SEF trip operations.
This setting is used to change the total number of the SEF trip
operations
[OPERATIONS]
Lockout-PHA: 4
Lockout-GND: 4
>Lockout-SEF: 4
[OPERATIONS]
Lockout-PHA: 4
>Lockout-GND: 4
Lockout-SEF: 4
[OPERATIONS]
>Lockout-PHA: 4
Lockout-GND: 4
Lockout-SEF: 4