3-Reclosers Loop control at F2 Fault
Figure 6-12. 3-Reclosers Loop control at F2 Fault
Step1 : When Permanent Fault occurs at F2, SEC(RC1) operates reclosing sequence and then Trip
Lockouts. During SEC(RC1) operation, accumulates Dead line time and the accumulated
time becomes “DL Pick T”. When a line is Dead Line, “LL Regain T” operates.
Step2 : “LL Regain T” is set, and if the line is not becoming Live line within a set time,
TIE(RC2) automatically changes to Alternate setting and close.
When closing TIE(RC2), MID(RC2) trip once and lockouts because of F2.
Step3 : After removing the fault, close SEC(RC1).
Step4 : Manually open TIE(RC2) and change to Primary setting.
Enable Loop control of TIE(RC2) and recover the line as the previous normal line.