RECLOSER CONTROL EVRC2A-N6,NT
http://www.entecene.co.kr
213
EN
HANCED
TEC
HNOLOGY
8.3. Trip Counter
8.3.1. Trip Counter Explanation
EVRC2A records counter related with System operation. Especially Trip Counter is operated
depending on Monitoring function set by user.
y
Trip :
Records trip operation count
y
Fault
: Records Fault count
y
System Restart :
Records system restart count
MAIN MENU / MAINTENANCE / COUNTERS
User can confirm in “
MAIN MENU/MAINTENANCE/COUNTERS”
8.3.2. Related Setting Menu
1)
Function Setting
Select for system to operate when Trip Counter reaches Limit value set by user.
PRIMARY SETTING / MONITORING / TRIP COUNTER / Function
Range
OFF, ALARM
Default
OFF
Step
~
OFF :
OFF Monitoring
ALARM :
Generate Alarm signal
2)
Alarm Output Relay Setting
Select Relay output for alarm.
PRIMARY SETTING / MONITORING / TRIP COUNTER / Relays(0-8)
Range
OFF, 0 ~ 8
Default
OFF
Step
1
Maximum 4 of Relay outputs can be selected to operate output signal.
0000(off) :
No Output Relay is selected.
1234 :
Operate output signal through 1, 2, 3, 4 Output Relay.
[TRIP COUNTER]
Function: OFF
>Relays(0-8): OFF
Limit: 10000
[TRIP COUNTER]
>Function: OFF
Relays(0-8): OFF
Limit: 10000
[ COUNTER ]
1.TRIP : 00000
2.FAULT : 00000
3.RESTART: 00011