12.1.1. Trigger Source
y
Occurred Protection element pickup
y
Occurred Fault trip command active
Depending on pickup size, if interval between pickup and trip is within 15 cycles including
prefault cycles(4 cycles), then record pickup cycles. But if the interval between pickup and trip
are not within 15 cycles, then record pickup cycles and trip cycles. These operations are very
useful to examine.
12.1.2. Data Channels
Stores following data :
y
5 currents : Ia, Ib, Ic, Ig, Isef
y
3 voltages (Va, Vb, Vc) : not passed digital-filter
y
85 logic input states
y
8Ch output relays
y
8Ch Inputs
12.1.3. Sample Rate
Captures one period of 16 sampling per cycle.
12.1.4. Storage capacity
The capacity of storage is last 32 events of 15cycles.
12.1.5. Related Setting Menu
1)
ON/OFF Setting
Fault Cycle waveform capture function can be set ON/OFF by user.
PRIMARY SETTING / RELAY SETUP \ EVENT RECORDER \ Fault Cycle
Range
OFF, ON
Default
ON
Step
~
ON :
Record fault cycle waveform.
OFF :
No record of fault cycle waveform.
[EVENT RECORDER]
>Fault Cycle: ON
Len' of Pre F: 4
Load Profile: ON