Commissioning
Proline t-mass A 150 HART
74
Hauser
4. Setting the write protection switch (WP) on the main electronics module to the ON
position enables the hardware write protection. Setting the write protection switch
(WP) on the main electronics module to the OFF position (factory setting) disables
the hardware write protection.
If the hardware write protection is enabled, the symbol appears before the
parameters in the header of the measured value display and in the navigation
view.
X X X X
X X X
X
X
20.50
XX
XX
A0015870
If the hardware write protection is disabled, the symbol does not appear before
the parameters in the header of the measured value display and in the navigation
view.
5. Feed the ribbon cable into the gap between the housing and electronics module and
plug the display module into the electronics compartment in the desired direction
until it engages.
6. Screw down the electronics compartment cover