Proline t-mass A 150 HART

Operation options

Hauser

39

The direct access code consists of a 4-digit number and the channel number, which

identifies the channel of a process variable: e.g. 0914-1. In the navigation view, this

appears on the right-hand side in the header of the selected parameter.

1

0914-2

  A0017223

1

Direct access code

Note the following when entering the direct access code:

• The leading zeros in the direct access code do not have to be entered.

Example: Input of "914" instead of "0914"

• If no channel number is entered, channel 1 is jumped to automatically.

Example: Input of "0914" → Parameter 

Totalizer 1

• If a different channel is jumped to: Enter the direct access code with the corresponding

channel number.

Example: Input of "0914-2" → Parameter 

Totalizer 2

For the direct access codes of the individual parameters →   110→   110

8.3.8  

Calling up help text

Help text is available for some parameters and can be called up from the navigation view.

The help text provides a brief explanation of the parameter function and thereby supports

swift and safe commissioning.

Calling up and closing the help text

The user is in the navigation view and the selection bar is on a parameter.

1. Press  for 2 s.

 The help text for the selected parameter opens.

Ent. access code
Enter access code to disable
write protec.

  A0014002-EN

 4

Example: Help text for parameter "Enter access code"

2. Press  +  simultaneously.

 The help text is closed.

Содержание Proline t-mass A 150

Страница 1: ...Products Solutions Services Operating Instructions Proline t mass A 150 HART Thermal mass flowmeter BA01042D 06 EN 03 20 71469730 2020 03 02 Valid as of version 01 00 zz Device firmware...

Страница 2: ...er to individuals or the facility read the Basic safety instructions section carefully as well as all other safety instructions in the document that are specific to working procedures The manufacturer...

Страница 3: ...on 23 7 1 Connection conditions 23 7 1 1 Required tools 23 7 1 2 Requirements for connecting cable 23 7 1 3 Requirements for the supply unit 23 7 1 4 Terminal assignment 24 7 1 5 Preparing the measuri...

Страница 4: ...to the process conditions 78 11 5 Performing a totalizer reset 78 11 6 Showing data logging 79 12 Diagnostics and troubleshooting 80 12 1 General troubleshooting 80 12 2 Diagnostic information on loca...

Страница 5: ...ol alerts you to a dangerous situation Failure to avoid this situation can result in minor or medium injury NOTICE A0011192 EN NOTICE This symbol contains information on procedures and other facts whi...

Страница 6: ...s or actions that are preferred A0011184 Forbidden Indicates procedures processes or actions that are forbidden A0011193 Tip Indicates additional information A0011194 Reference to documentation Refers...

Страница 7: ...rdance with the Pressure Equipment Directive Instructions in the relevant supplementary documentation must be consistently observed The supplementary documentation is an integral part of the device do...

Страница 8: ...easuring device in full compliance with the data on the nameplate and the general conditions listed in the Operating Instructions and supplementary documentation Based on the nameplate check whether t...

Страница 9: ...he device Wear the required personal protective equipment according to federal national regulations For welding work on the piping Do not ground the welding unit via the measuring device 2 4 Operation...

Страница 10: ...96 1 Electronics compartment cover 2 Display module 3 Terminal block 4 Electronics module 5 Cable gland 6 Transmitter housing 7 Sensor 8 S DAT 3 2 Registered trademarks HART Registered trademark of th...

Страница 11: ...ptance A0015502 1 2 1 2 A0013843 Is the order code on the delivery note 1 identical to the order code on the product sticker 2 A0013695 A0015502 A0013698 Are the goods undamaged A0015502 A0013699 Do t...

Страница 12: ...nt documentation 7 The W M Device Viewer Enter the serial number from the nameplate www endress com deviceviewer 4 2 1 Transmitter nameplate Patents i i Order code Ext ord cd Ser no 1 2 3 4 5 6 7 8 9...

Страница 13: ...er nominal pressure 10 Approval information for Pressure Equipment Directive 11 Manufacturing date year month Order code The measuring device is reordered using the order code Extended order code The...

Страница 14: ...he webbing slings Observe the following notes during transport Transport the measuring device to the measuring point in the original packaging Lifting gear Webbing slings Do not use chains as they cou...

Страница 15: ...on trap thermal insulation etc Orientation The direction of the arrow on the sensor helps you to install the sensor according to the flow direction direction of medium flow through the piping Vertical...

Страница 16: ...d 14511 A0005103 Correctly aligned flanges and seals A0005105 A0005106 A0005104 Incorrectly sized seal Incorrectly aligned flanges and seals Internal diameter of pipe does not correspond to internal d...

Страница 17: ...ce see the Technical Information document Mechanical construction section Outlet run for pressure or temperature transmitter If a pressure or temperature measuring device is installed downstream of th...

Страница 18: ...easurement accuracy 1 2 2 3 4 1 1 1 A0005116 1 Flow conditioner 2 Seal 3 Alignment notch 4 Correctly align the alignment notch and transmitter Not suitable for lap joint flange or threaded versions Or...

Страница 19: ...9 to 60 C 20 2 to 140 F Local display 20 to 60 C 4 to 140 F The readability of the display may be impaired at temperatures outside the temperature range If operating outdoors Avoid direct sunlight par...

Страница 20: ...er process sealing Ensure that the inside diameters of the gaskets are greater than or equal to that of the measuring tube and piping Ensure that the gaskets are clean and undamaged In the case of lap...

Страница 21: ...le to the desired position Max 4 90 in each direction 4 Feed the ribbon cable into the gap between the housing and main electronics module and plug the display module into the electronics compartment...

Страница 22: ...of flow of the medium through the piping 15 Have sufficient inlet and outlet runs been provided upstream and downstream of the measuring point Correctly aligned in the direction of flow Is the device...

Страница 23: ...m requirement for cable temperature range ambient temperature 20 K Current output For 4 20 mA HART Shielded cable recommended Observe grounding concept of the plant Pulse frequency switching output St...

Страница 24: ...ble glands corresponding to the degree of protection If measuring device is delivered without cable glands Provide suitable cable gland for corresponding connecting cable 23 3 If measuring device is d...

Страница 25: ...mmunication When connecting the cable shielding to the ground terminal observe the grounding concept of the facility 6 Firmly tighten the screws in the terminal block 7 Perform the same steps for the...

Страница 26: ...4 Post connection check Are cables or the device undamaged visual inspection Are the power supply and signal cables correctly connected Does the supply voltage correspond to the specifications in the...

Страница 27: ...ay module 2 Computer with operating tool e g FieldCare AMS Device Manager SIMATIC PDM 3 Field Xpert SFX100 4 Field Communicator 475 5 Control system e g PLC 8 2 Structure and function of the operating...

Страница 28: ...experts Language Display operat Access status display Locking status Operation Setup Wizard 1 Parameter 1 Wizard 2 Parameter 2 Wizard n Parameter n Advanced setup Enter access code Parameter 1 Parame...

Страница 29: ...ion event messages that have occurred Device information submenu Contains information for identifying the device Measured values submenu Contains all current measured values Data logging submenu order...

Страница 30: ...service mode e g during a simulation A0013958 Out of specification The device is being operated Outside its technical specification limits e g outside the process temperature range Outside of the conf...

Страница 31: ...711 Corrected volume flow FAD A0013710 Mass flow A0013947 Temperature A0013943 Totalizer A0013945 Current output Measurement channel numbers Symbol Meaning A0016325 Measurement channel 1 to 4 The meas...

Страница 32: ...the wizard Display symbol for wizard Omission symbol for operating menu levels in between Name of current Submenu Wizard Parameter Examples A0013973 Display A0013968 Display For more information about...

Страница 33: ...0013966 Expert Appears In the menu next to the Expert selection At the left in the navigation path in the Expert menu Submenus wizards parameters Symbol Meaning A0013967 Submenu A0013968 Wizard A00139...

Страница 34: ...ric editor Symbol Meaning 0 9 A0013998 Selection of numbers from 0 to 9 A0016619 Inserts decimal separator at the input position A0016620 Inserts minus sign at the input position A0013985 Confirms sel...

Страница 35: ...left A0013988 Deletes one character immediately to the left of the input position 8 3 4 Operating elements Key Meaning A0013969 Minus key In a menu submenu Moves the selection bar upwards in a choose...

Страница 36: ...to the next higher level If help text is open closes the help text of the parameter Pressing the key for 2 s returns you to the operational display home position With a Wizard Exits the wizard and ta...

Страница 37: ...er 37 2 Press simultaneously The context menu is closed and the measured value display appears Calling up the menu via the context menu 1 Open the context menu 2 Press to navigate to the desired menu...

Страница 38: ...0098 1 0098 1 XXXX XXX X X 10 50 19 00 XX XX XX XX Display operat Display operat Setup Main menu English Main menu Format display Display Contrast display Display intervall 1 value max Setup Access st...

Страница 39: ...talizer 1 If a different channel is jumped to Enter the direct access code with the corresponding channel number Example Input of 0914 2 Parameter Totalizer 2 For the direct access codes of the indivi...

Страница 40: ...mple Changing the parameter 20 mA value to 20 kg s 3 4 0 2 9 5 6 8 7 l h 2x 20 000 l h 0 000 l h 100 000 l h 0 000 l h 100 000 3 4 0 1 2 9 5 6 8 7 l h 100 000 1 3 4 0 1 2 9 5 6 8 7 l h 0 3 4 0 1 2 9 5...

Страница 41: ...ess rights of the Operator role The user role with which the user is currently logged on is indicated by the Access status display parameter Navigation path Display operation Access status display 8 3...

Страница 42: ...simultaneously pressing the keys After enabling the keypad lock XXXXXXXXXX kg h 20 50 Keylock on A0014000 EN After disabling the keypad lock XXXXXXXXXX kg h 20 50 Keylock off A0014001 EN If the user...

Страница 43: ...r It can configure all smart field devices in a system and helps you manage them By using the status information it is also a simple but effective way of checking their status and condition Access tak...

Страница 44: ...4 5 Field Communicator 475 Function scope Industrial handheld terminal from Emerson Process Management for remote configuration and measured value display via HART protocol Source for device descript...

Страница 45: ...T Operation options Endress Hauser 45 Via service interface CDI 1 2 3 E A0017253 1 Service interface CDI of the measuring device Endress Hauser Common Data Interface 2 Commubox FXA291 3 Computer with...

Страница 46: ...for the individual operating tools is listed in the table below along with information on where the file can be acquired Operating tool via HART protocol Sources for obtaining device descriptions Fiel...

Страница 47: ...ign TV Expert Communication HART output Output Assign QV The following measured variables can be assigned to the dynamic variables Measured variables for PV primary dynamic variable Mass flow Correcte...

Страница 48: ...fter a successful startup the local display switches automatically from the startup display to the measured value display If nothing appears on the local display or a diagnostic message is displayed r...

Страница 49: ...XXX X X 20 50 0104 1 XXXXXXXXX XXXXXXXXX mA Display operat Setup Diagnostic Display operat Setup Main menu English Main menu Select gas type Setup Language A0017371 EN Overview of the Setup menu Setu...

Страница 50: ...sure Parameter overview with brief description Parameter Description Selection User entry Factory setting Process pressure Process pressure value for calculating pressure dependent gas properties 0 5...

Страница 51: ...the value for the 20 mA current The value can be larger than or smaller than the 4 mA value assigned Positive and negative values are permitted depending on the measured variable e g mass flow assigne...

Страница 52: ...tch off value Enter the measured value for the switch off value Depends on the process variable selected Switch on value Enter the measured value for the switch on value Depends on the process variabl...

Страница 53: ...104 1 0092 1 XXXXXXXXX XXXXXXXXX XXXXXXXXX XXXXXXXXX mA Display operat Setup Diagnostic Display operat Setup Main menu English Main menu Select gas type Setup Setup Advanced setup Ent access code Adva...

Страница 54: ...layed depends on the characters used 10 5 2 Configuring applications Navigation path Setup menu Advanced setup Applications Parameter overview with brief description Applications Select gas type Proce...

Страница 55: ...eference pressure Enter the reference pressure for calculating the reference density 0 1 to 99 bar a 1 5 to 1436 psi a Country dependent 1 0130 bar a 14 696 psi a Reference temperature Enter the refer...

Страница 56: ...lect the unit for mass flow Result The selected unit applies for all outputs Metric Gram g s g min g h g day Kilogram kg s kg min kg h kg day Metric ton t s t min t h t day US Ounce oz s oz min oz h o...

Страница 57: ...FAD min m FAD h m FAD d cf FAD s cf FAD min cf FAD h cf FAD d Country dependent m FAD h cf FAD min FAD volume unit Select the unit for standard volume l FAD m FAD cf FAD Country dependent m FAD cf FA...

Страница 58: ...User entry Factory setting Assign current output Use this function to assign a measured variable or process variable to the current output Mass flow Corrected volume flow FAD volume flow Temperature M...

Страница 59: ...unit applies for all outputs C F K R Country dependent C Celsius F Fahrenheit Current span Select the current range for the process value output and for the upper lower level for signal on alarm Optio...

Страница 60: ...condition Floating point number with 2 decimal places in the range3 6 to 22 5 mA 22 5 mA 10 5 5 Configuring the PFS output In the PFS output submenu you can configure the values for the current outpu...

Страница 61: ...ut Off Mass flow Corrected volume flow FAD volume flow Off Assign frequency output Select the process variable for the frequency output Off Mass flow Corrected volume flow FAD volume flow Temperature...

Страница 62: ...g t oz lb STon LTon User defined Country dependent kg lb FAD volume flow unit Use this function to select the preferred unit that is to be displayed for the FAD volume flow The following time units ca...

Страница 63: ...alue Max current Minimum frequency value Enter the minimum frequency value 0 to 1000 Hertz 0 Hertz Maximum frequency value Enter the maximum frequency value 0 to 1000 Hertz 1000 Hertz Measuring value...

Страница 64: ...ry setting Failure mode Specify the output behavior in the event of a device alarm Failsafe mode The failsafe mode defines how the pulse output responds to a status message which is supposed to act on...

Страница 65: ...t Display damping Current output Response time Damping PFS output Response time Damping Parameter overview with brief description Parameter Description Selection User entry Factory setting Display dam...

Страница 66: ...er overview with brief description Parameter Description Selection User entry Factory setting Assign process variable Select the process variable for low flow cut off Off Mass flow Corrected volume fl...

Страница 67: ...ng options is selected in the Assign process variable parameter Mass flow Corrected volume flow FAD volume flow Select the unit for the process variable of the totalizer Unit choose list Country depen...

Страница 68: ...rected volume flow FAD volume flow Temperature Totalizer Current output None Decimal places 2 Select the number of decimal places for the display value x x x x xx x xxx x xxxx x xx Value 3 display Sel...

Страница 69: ...configuration copy it to another measuring point or restore the previous device configuration You can do so using the Configuration management parameter and the related options found in the Conf back...

Страница 70: ...nu enables you to simulate without a real flow situation various process variables in the process and the device alarm mode and to verify downstream signal chains switching valves or closed control lo...

Страница 71: ...The On option is selected in the Frequency simulation parameter Enter the frequency for simulation 0 0 to 1250 Hz Frequency currently measured Pulse simulation Pulse must be selected in the Operating...

Страница 72: ...he totalizer Language Format display Resetting the totalizer Contrast display Display interval The device automatically locks the write protected parameters again if a key is not pressed for 10 minute...

Страница 73: ...E ON OFF 1 2 1 2 A0017255 1 Unscrew the electronics compartment cover 2 Pull out the display module with a gentle rotational movement 3 A0017375 To make it easier to access the lock switch attach the...

Страница 74: ...ection is enabled the symbol appears before the parameters in the header of the measured value display and in the navigation view XXXX XXX X X 20 50 XX XX A0015870 If the hardware write protection is...

Страница 75: ...entry Factory setting Format display Select how measured values are shown on the display 1 value max size 1 bargraph 1 value 2 values 1 value large 2 values 4 values 1 value max size Contrast display...

Страница 76: ...ly calculated Floating point number with sign Corrected volume flow Displays the calculated volume flow Floating point number with sign FAD volume flow Displays the FAD volume flow currently calculate...

Страница 77: ...ameters needed to display the current measured values for every output Navigation path Diagnostics menu Measured values Output values Structure of the submenu Output values Output current Pulse output...

Страница 78: ...d and the totalizer is set to the defined start value in the Preset parameter Reset totalize The totalizer is reset to 0 and the totaling process is restarted Preset totalize The totalizer is set to t...

Страница 79: ...interval Clear data Display channel 1 Display channel 2 Display channel 3 Display channel 4 Function range A total of 1000 measured values can be stored 4 logging channels Adjustable logging interval...

Страница 80: ...y darker by simultaneously pressing Local display is dark but signal output is within the valid current range 3 6 to 22 mA Ribbon cable of the display module is not plugged in correctly Insert the plu...

Страница 81: ...erface on computer configured incorrectly Observe the documentation for the Commubox FXA 191 HART Document Technical Information TI00237F FXA 195 HART Document Technical Information TI00404F No connec...

Страница 82: ...A0013959 Function check The device is in service mode e g during a simulation A0013958 Out of specification The device is being operated Outside its technical specification limits e g outside the proc...

Страница 83: ...stic behavior Status signal Diagnostic number Short text Example A0013962 A0013958 441 Curr output 1 3 digit number If two or more diagnostic events are pending simultaneously only the message with th...

Страница 84: ...stic event with or and press The message for the remedial measures for the selected diagnostic event opens 3 Press simultaneously The message about the remedial measures closes The user is in the Diag...

Страница 85: ...stic number is assigned a specific diagnostic behavior at the factory The user can change this assignment for specific diagnostic numbers via the Diagnostics No xxx parameter Navigation path Expert me...

Страница 86: ...edy information Status signal from the factory Diagnostic behavior from the factory Diagnostics for the electronics 270 Main electronic failure Change main electronic module F Alarm 271 Main electroni...

Страница 87: ...utput 1 Check process 2 Check pulse output setting S Warning 453 Flow override Deactivate flow override C Warning 484 Simulation failsafe mode Deactivate simulation C Alarm 485 Simulation process vari...

Страница 88: ...y defaults Every parameter is reset to the factory setting To delivery settings Every parameter for which a customer specific default setting was ordered is reset to this customer specific value All o...

Страница 89: ...ries can be displayed The event history includes entries for Diagnostic events 80 Information events 80 In addition to the operation time of its occurrence each event is also assigned a symbol that in...

Страница 90: ...ogbook only and not in the diagnostic list Information event Event text I1000 device ok I1089 Power on I1090 Configuration reset I1091 Configuration changed I1092 Trend data deleted I1110 Write protec...

Страница 91: ...ficates Document every repair and each conversion and enter them into the W M life cycle management database 13 2 Spare parts Some interchangeable measuring device components are identified by an over...

Страница 92: ...When cleaning make sure that the transducers are not damaged Never use cleaning agents that can corrode the material and the seal Sensor specific information If the sensor gland is opened the accurac...

Страница 93: ...ng points for returning the device Contact your Endress Hauser Sales Center to obtain information about the procedure and basic conditions Enclose the completed Decontamination declaration form with t...

Страница 94: ...Connecting the measuring device in the logically reverse sequence Observe the safety instructions 16 2 Disposing of the measuring device LWARNING Danger to personnel and environment from fluids that a...

Страница 95: ...tic values Measured variable Direct measured variables Mass flow Gas temperature Calculated measured variables Corrected volume flow FAD free air delivery volume flow Measuring range The available mea...

Страница 96: ...DIN flange versions DN kg h Nm3 h at 0 C 1 013 bar a Nm3 h at 15 C 1 013 bar a mm min Max min Max min Max 15 0 5 80 0 38 62 0 24 65 25 2 300 1 5 232 1 0 245 40 6 833 4 6 644 2 3 681 50 10 1365 7 7 10...

Страница 97: ...imum input values DC30 V 25 mA Voltage drop For 25 mA DC2 V Pulse output Pulse width Adjustable 0 5 to 2000 ms pulse rate 0 to 1000 Pulse s Pulse value Adjustable Assignable measured variables Mass fl...

Страница 98: ...tus Open Closed Local display Plain text display With information on cause and remedial measures Status signal as per NAMUR recommendation NE 107 Operating tool Via digital communication HART protocol...

Страница 99: ...talizer 17 5 Power supply Terminal assignment Transmitter Connection version 4 20 mA HART pulse frequency switching output 4 1 2 3 1 2 2 3 2 2 2 4 2 5 2 6 2 7 A0017178 1 Supply voltage 2 Signal transm...

Страница 100: ...output Option K Pulse frequency switching output 185 mA 2 5 A Power supply failure Totalizers stop at the last value measured Configuration is retained in the device memory Error messages incl total o...

Страница 101: ...g conditions Calibration systems traceable to national standards Accredited in accordance with ISO IEC 17025 Air controlled to 24 C 0 5 C 75 2 F 0 9 F at atmospheric pressure Humidity controlled 40 RH...

Страница 102: ...sures within the specified tolerance G Q 1 to 100 5 o f s under reference conditions This version is subject to neither a calibration nor a verification of measuring performance Accuracy of outputs Cu...

Страница 103: ...sor Flange and threaded connection made of stainless steel 40 to 100 C 40 to 212 F Flange connection PN16 made of carbon steel 10 to 100 C 14 to 212 F Flange connection Cl 150 made of carbon steel 29...

Страница 104: ...joint flange Threaded version CL300 PN40 PN16 PN10 CL150 15 4 0 3 9 4 1 3 2 3 4 2 6 25 5 5 4 8 5 0 3 5 4 3 2 6 40 7 9 7 0 7 5 4 9 6 1 3 1 50 9 9 9 3 9 4 5 9 8 0 3 8 Weight in US units Compact version...

Страница 105: ...4 1 4435 as per EN 10216 5 Stainless steel 316L as per ASTM A312 Measuring tube DN 15 in Stainless steel 1 4404 as per EN 10272 EN10216 5 Stainless steel 316 316L as per ASTM A479 ASTM A312 DN 25 to 5...

Страница 106: ...cient diagnostics increase measurement reliability Remedial information is integrated in plain text Diverse simulation options and optional line recorder functions Local operation Display Operation Or...

Страница 107: ...switching output 1 2 3 5 4 6 7 A0017373 8 Options for remote operation via HART protocol 1 Control system e g PLC 2 Field Communicator 475 3 Computer with operating tool e g FieldCare AMS Device Mana...

Страница 108: ...Class I Pressure Equipment Directive With the PED G1 x x category marking on the sensor nameplate Endress Hauser confirms compliance with the Essential Safety Requirements specified in Annex I of the...

Страница 109: ...14 Documentation The following document types are available On the CD ROM supplied with the device In the Download Area of the Endress Hauser Internet site www endress com Download Standard documenta...

Страница 110: ...nd in the manual Language 0104 48 Display operat 27 Display 75 Format display 0098 75 Contrast display 0105 75 Display interval 0096 75 Operation 75 Control totalizer 0912 78 Preset value 0913 78 Rese...

Страница 111: ...code 0093 72 Device tag 0215 54 Applications 54 Select gas type 3381 55 Process pressure 3376 55 Temperature 1853 55 Reference conditions 3439 55 Reference pressure 3378 55 Reference temperature 3379...

Страница 112: ...D volume flow unit 0601 58 Temperature unit 0557 58 Current span 353 58 4mA value 367 58 20mA value 372 58 Failure mode 364 58 Failure current 352 58 PFS output 60 Operating mode 0469 61 Assign pulse...

Страница 113: ...4 61 Minimum frequency value 0453 61 Measuring value at minimum frequency 0476 61 Measuring value at maximum frequency 0475 61 Measuring value at maximum frequency 0475 61 Measuring value at minimum f...

Страница 114: ...lue low flow cutoff 1805 66 Off value low flow cutoff 1804 66 Totalizer 67 Assign process variable 0914 67 Unit 0915 67 Failure mode 901 67 Display 67 Format display 0098 67 Value 1 display 0107 68 0...

Страница 115: ...69 Configuration management 0100 70 Comparison result 0103 70 Diagnostics 80 Actual diagnostics 0691 80 Previous diagnostics 0690 80 Operating time from restart 0653 Operating time 0652 69 Diagnostics...

Страница 116: ...76 Mass flow 1838 76 Corrected volume flow 1847 76 FAD volume flow 1851 76 Temperature 1853 76 Totalizer 76 Totalizer value 0911 77 Totalizer overflow 0910 77 Output values 77 Output current 0361 77...

Страница 117: ...rent output 1 0355 71 Frequency simulation 0472 71 Frequency value 0473 71 Pulse simulation 0458 71 Pulse value 0459 71 Switch output simulation 0462 71 Switch status 0463 71 Simulation device alarm 0...

Страница 118: ...argraph value 3 0126 68 Decimal places 3 0118 68 Value 4 display 0109 68 Decimal places 4 0119 69 Display interval 0096 69 Display damping 0094 69 Header 0097 69 Header text 0112 69 Separator 0101 69...

Страница 119: ...3 76 Totalizer 76 Totalizer value 0911 77 Totalizer overflow 0910 77 Output values 77 Output current 0361 77 Pulse output 1 to 2 0456 77 Output frequency 1 to 2 0471 77 Switch status 1 to 2 0461 77 Sy...

Страница 120: ...66 Assign process variable 1837 66 On value low flow cutoff 1805 66 Off value low flow cutoff 1804 66 Calculated value Reference values Reference conditions 3439 55 Reference pressure 3378 55 Referen...

Страница 121: ...ce in use 3440 Flow reference value 1 3401 Power coefficient 1 3425 Flow reference value 2 3418 Power coefficient 2 3426 Flow reference value 3 3419 Power coefficient 3 3427 Flow reference value 4 342...

Страница 122: ...3529 Flow reference value 1 3384 Power coefficient 1 3392 Flow reference value 2 3385 Power coefficient 2 3393 Flow reference value 3 3386 Power coefficient 3 3394 Flow reference value 4 3387 Power c...

Страница 123: ...7 Assign current output 359 58 Current span 353 Fixed current 365 4mA value 367 20mA value 372 Damping 363 65 Response time 378 65 Failure mode 364 Output current 361 77 Start up mode 368 PFS output 1...

Страница 124: ...ion 481 52 Assign diagnostic behavior 482 61 Assign limit 483 61 Switch on value 466 52 Switch off value 464 52 Assign status 485 52 Switch on delay 467 61 Switch off delay 465 61 Failure mode 486 61...

Страница 125: ...Primary variable PV 201 46 Assign SV 235 46 Secondary variable SV 226 46 Assign TV 236 46 Tertiary variable TV 228 46 Assign QV 237 46 Quaternary variable QV 203 46 Application Reset all totalizers 28...

Страница 126: ...o 46 Device tag 11 91 Serial number 9 91 Firmware version 10 46 Device name 13 46 Order code 8 46 Extended order code 1 23 46 Extended order code 2 21 46 Extended order code 3 22 46 ENP version 12 46...

Страница 127: ...rature Minimum value 3447 Maximum value 3446 Simulation 70 Assign process variable 1810 71 Value process variable 1811 71 Simulation current output 1 354 71 Value current output 1 355 71 Frequency sim...

Страница 128: ...ation 36 Current consumption 100 D Declaration of Conformity 9 Declaration of Contamination 93 Define access code 72 Degree of protection 25 103 Design Measuring device 10 Designated use 8 Device comp...

Страница 129: ...43 SIMATIC PDM 44 Function scope Field Communicator 44 Field Communicator 475 44 Functions see Parameter G Galvanic isolation 98 H HART protocol Device variables 46 Measured variables 46 Revision 46 H...

Страница 130: ...tenance 110 Operating philosophy 29 Operating tools Connection overview 44 Operation 75 Operation options 27 Operational display 30 Operational safety 9 Order code 12 13 Orientation vertical horizonta...