Proline Prosonic Flow P 500
26
Hauser
Supported baud rate
• 1
200 BAUD
• 2
400 BAUD
• 4
800 BAUD
• 9
600 BAUD
• 19
200 BAUD
• 38
400 BAUD
• 57
600 BAUD
• 115
200 BAUD
Data transfer mode
• ASCII
• RTU
Data access
Each device parameter can be accessed via Modbus RS485.
For Modbus register information
System integration
Information on system integration: Operating Instructions .
• Modbus RS485 information
• Function codes
• Register information
• Response time
• Modbus data map
Power supply
Terminal assignment
Transmitter: supply voltage, input/outputs
HART
Supply voltage
Input/output
1
Input/output
2
Input/output
3
1 (+)
2 (–)
26 (+)
27 (–)
24 (+)
25 (–)
22 (+)
23 (–)
Device-specific terminal assignment: adhesive label in terminal cover..
Modbus RS485
Supply voltage
Input/output
1
Input/output
2
Input/output
3
1 (+)
2 (–)
26 (B)
27 (A)
24 (+)
25 (–)
22 (+)
23 (–)
Device-specific terminal assignment: adhesive label in terminal cover..
Transmitter and sensor connection housing: connecting cable
The sensor and transmitter, which are mounted in separate locations, are interconnected by a
connecting cable. The cable is connected via the sensor connection housing and the transmitter
housing.
Terminal assignment and connection of the connecting cable:
Device plugs available
Device plugs may not be used in hazardous areas!
Device plug for connecting to the service interface:
Order code for "Accessory mounted"
option
NB
Содержание Proline Prosonic Flow P 500
Страница 78: ......
Страница 79: ......
Страница 80: ...www addresses endress com 71508895 71508895...