Proline Prosonic Flow P 500
Hauser
25
Order code for
"Output; input 2";
"Output; input 3"
Output type
Intrinsically safe values or NIFW values
Output; input 2
Output; input 3
24 (+)
25 (–)
22 (+)
23 (–)
Option C
Current output 4 to 20 mA
Ex i passive
U
i
= 30 V
l
i
= 100 mA
P
i
= 1.25 W
L
i
= 0
C
i
= 0
Option G
Pulse/frequency/switch
output Ex i passive
U
i
= 30 V
l
i
= 100 mA
P
i
= 1.25 W
L
i
= 0
C
i
= 0
Low flow cut off
The switch points for low flow cut off are user-selectable.
Galvanic isolation
The outputs are galvanically isolated from one another and from earth (PE).
The clamp-on sensors can also be mounted on cathodically protected pipes
.
Protocol-specific data
HART
Manufacturer ID
0x11
Device type ID
0x5D (93)
HART protocol revision
7
Device description files
(DTM, DD
)
Information and files under:
HART load
Min. 250 Ω
System integration
Information on system integration: Operating Instructions → 76.
• Measured variables via HART protocol
• Burst Mode functionality
Modbus RS485
Protocol
Modbus Applications Protocol Specification V1.1
Response times
• Direct data access: typically 25 to 50 ms
• Auto-scan buffer (data range): typically 3 to 5 ms
Device type
Slave
Slave address range
1 to 247
Broadcast address range
0
Function codes
• 03: Read holding register
• 04: Read input register
• 06: Write single registers
• 08: Diagnostics
• 16: Write multiple registers
• 23: Read/write multiple registers
Broadcast messages
Supported by the following function codes:
• 06: Write single registers
• 16: Write multiple registers
• 23: Read/write multiple registers
4)
Only DN 50 to 4000 (2 to 160") and non-Ex