Output signal
Current output 4 to 20 mA HART
Order code
"Output; input 1" (20):
Option BA: current output 4 to 20 mA HART
Signal mode
Can be set to:
• Active
• Passive
Current range
Can be set to:
• 4 to 20 mA NAMUR
• 4 to 20 mA US
• 4 to 20 mA
• 0 to 20 mA (only if the signal mode is active)
• Fixed current
Open-circuit voltage
DC 28.8 V (active)
Maximum input voltage
DC 30 V (passive)
Load
250 to 700 Ω
Resolution
0.38 µA
Damping
Configurable: 0 to 999.9 s
Assignable measured
variables
• Volume flow
• Mass flow
• Sound velocity
• Flow velocity
• Electronics temperature
The range of options increases if the measuring device has one or more
application packages.
Current output 4 to 20 mA HART Ex i
Order code
"Output; input 1" (20) choose from:
• Option CA: current output 4 to 20 mA HART Ex i passive
• Option CC: current output 4 to 20 mA HART Ex i active
Signal mode
Depends on the selected order version.
Current range
Can be set to:
• 4 to 20 mA NAMUR
• 4 to 20 mA US
• 4 to 20 mA
• 0 to 20 mA (only if the signal mode is active)
• Fixed current
Open-circuit voltage
DC 21.8 V (active)
Maximum input voltage
DC 30 V (passive)
Load
• 250 to 400 Ω (active)
• 250 to 700 Ω (passive)
Resolution
0.38 µA
Damping
Configurable: 0 to 999.9 s
Assignable measured
variables
• Volume flow
• Mass flow
• Sound velocity
• Flow velocity
• Electronics temperature
The range of options increases if the measuring device has one or more
application packages.