Proline Prosonic Flow P 500
Hauser
39
1
2
15 × DN
3 × DN
15 × DN
3 × DN
3
4
15 × DN
3 × DN
5
6
15 × DN
3 × DN
a
b
20 × DN
3 × DN
20 × DN
3 × DN
A0042041
26
Minimum inlet and outlet runs with various flow obstructions
1
Pipe bend
2
Two pipe bends (on one plane)
3
Two pipe bends (on two planes)
4a reduction
4b Expansion
5
Control valve (2/3 open)
6
Pump
Mounting the sensor
L
WARNING
Risk of injury when mounting the sensors and strapping bands!
‣
Due to the increased risk of cuts, wear suitable gloves and protective goggles.
Sensor configuration and settings
DN 15 to 65 (½ to 2½")
DN 50 to 4000 (2 to 160")
Strapping band
Strapping band
Welded bolt
2 traverses
[mm (in)]
1 traverse
[mm (in)]
2 traverses
[mm (in)]
1 traverse
[mm (in)]
2 traverses
[mm (in)]
Sensor distance
Sensor distance
Sensor distance
Sensor distance
Sensor distance
–
Wire length → 47
Measuring rail
Wire length
Measuring rail
1)
Depends on the conditions at the measuring point (measuring pipe, medium etc.). The dimension can be
determined via FieldCare or Applicator. See also the
Result sensor distance / measuring aid
parameter in
the
Measuring point
submenu
2)
Only up to DN 600 (24")
Mounting types
Sensor holder with U-shaped screws
Can be used for
• Measuring devices with measuring range DN 15 to 65 (½ to 2½")
• Mounting on pipes DN 15 to 32 (½ to 1¼")
Procedure:
1. Disconnect the sensor from the sensor holder.
2. Position the sensor holder on the measuring pipe.
3. Fit the U-shaped screws through the sensor holder and lightly grease the thread.