Commissioning
Micropilot M FMR231 with FOUNDATION Fieldbus
66
Hauser
6.6.5
Connection of the function blocks
1.
A concluding overall system configuration is essential so that the operating mode of the Analog
Input Block can be set to AUTO and so that the field device is integrated into the system
application. To do this, a configuration software (e.g. you host system software) is used to
connect the function blocks - normally graphically - to the desired control strategy and then
the sequence of the individual process control functions is specified.
NI-FBUS-FMxxx-en-001
Example: Connection of the function blocks with the NI-FBUS Configurator
2.
Download the configuration data into the field devices by the download function of the
FOUNDATION Fieldbus configuration tool.
3.
Set the oerating mode of the AI Block to AUTO (parameter group MODE_BLK, parameter
TARGET). However, this is only possible under the following conditions:
– The function blocks are correctly connected with each other.
– The parametrization of the AI Block is correct (see 6.6.4, steps 5 and 6).
– The Resource Block is in operating mode AUTO.