Micropilot M FMR231 with FOUNDATION Fieldbus
Commissioning
Hauser
43
6.3
Resetting the device
It is advisable to reset the device parameters before the commissioning if you want to use a device
with an unknown history.
6.3.1
Resetting the parameters of the FOUNDATION Fieldbus func-
tion blocks
Parameters affected
• all parameters of the FOUNDATION Fieldbus function blocks
L00-FMU4XXXX-02-00-00-YY-007
Performing the reset
Resource Block, parameter RESTART; select the option "defaults".
6.3.2
Resetting the parameters of the transducer blocks
"
Caution!
A reset may lead to impairment of the measurement. As a rule, a basic calibration is required after
a reset.
!
Note!
The default values of each parameter are shown in bold in the menu overview in the appendix.
In order to carry out the reset, enter the number "33333" in the
"reset" (0A3)
function in the
"diagnostics" (0A)
function group.
(FOUNDATION Fieldbus:
Diagnostic Block
, Parameter
PARRESET (reset)
)
Parameters affected
• all parameters of the device specific blocks (Sensor Block, Diagnostic Block, Display Block)
L00-FMU4XXXX-02-00-00-YY-008
Effects of the reset
• All customer parameters are reset to their default values.
• Customer interference echo suppression is
not
deleted.
Hauser
Service-Parameter
Sensorblock
Diagnoseblock
Display-Block
Resource Block
AI-Block 1
AI-Block 2
PID Block
Arithmetik-Block
Input-Selector-Block
Signal-Charact.-Block
Integrator-Block
Hauser
Service-Parameter
Sensorblock
Diagnoseblock
Display-Block
Resource Block
AI-Block 1
AI-Block 2
PID Block
Arithmetik-Block
Input-Selector-Block
Signal-Charact.-Block
Integrator-Block