8
GB
8
2-PIPE THIN VERSION TECHNICAL SPECIFICATIONS
See the table in figure 5 and refer to the relevant model.
A
Coil water content
C
Maximum operating pressure
D
Maximum water inlet temperature
E
Minimum water inlet temperature
F
Hydraulic connections
G
Supply voltage
H
Absorbed max current
I
Absorbed max power
M
Weight of ETI
N
Weight of ETM
5
ℓ
bar
°C
°C
“
V/ph/Hz
A
W
kg
kg
A
C
D
E
F
G
H
I
M
N
220
0.47
10
80
4
Eurokonus 3/4
230/1/50
0.11
11.9
9
17
240
0.8
10
80
4
Eurokonus 3/4
230/1/50
0.16
17.6
12
20
260
1.13
10
80
4
Eurokonus 3/4
230/1/50
0.18
19.8
15
23
280
1.46
10
80
4
Eurokonus 3/4
230/1/50
0.26
26.5
18
26
MOD.
INSTALLATION
POSITIONING THE
UNIT
Do not install the unit near
:
- anything that is subject to
direct exposure to sunlight;
- sources of heat;
- damp environments and
areas with probable contact
with water;
- environments with oil vapours
- environments subjected to
high frequencies.
Make sure that:
- the wall on which the unit is to
be installed has an adequate
structure and capacity;
- the area of the wall in question
has no pipes or electric lines
passing
- the wall in question is perfectly
level;
- there is an area free from
obstacles, which could
compromise the input and
output air circulation;
- the installation wall is possibly
an external perimeter wall
so as to allow the outward
condensate drain;
- in case of a ceiling installation,
the air flow is not directed
directly towards people.
INSTALLATION METHOD
The following descriptions of
the various assembly phases
and the relative drawings refer
to a machine version with
connections on the left.
The descriptions for machine
assembly operations with
connections on the right are
the same.
The images just have to be
considered specular.
Carefully follow the instructions
in this manual for a successful
i n s t a l l a t i o n a n d o p t i m a l
operating performance. Failure
to apply the indicated standards,
which can cause equipment
malfunctions, relieve EMMETI
from any form of warranty and
from any damage caused to
people, animals or property.
It is important for the electrical
installation to be executed in
accordance with the law, for it to
conform to the data indicated in
the technical data sheet and for
it to consist of a good earthing
system.
The appliance must be installed
in a position that easily allows
routine (filter cleaning) and
special maintenance to be
performed, as well as access
to the air vent valves (coil and
plates), which can be reached
from the top grid on the
connections side.
2100
1.8
10
80
4
Eurokonus 3/4
230/1/50
0.28
29.7
21
29