Assembling the air temperature probe
Electrical box connections THIN-4-V
Water probe management of the electrical box THIN-4-V
B
C
D
A
C
A
D
PE
N
L
H2
water temperature probe 10 kΩ
M1
DC inverter fan motor
S1
grid safety microswitch
Y1
water solenoid valve (230V / 50Hz 1A voltage output)
L-N
230V / 50Hz power supply connection
Electrical boxconnections THIN-4-V
To position the temperature probe (ref. A):
-
pass the probe through the hole of the edge (ref. B)
-
insert the probe in the lower hole (ref. C)
-
secure the probe in the relevant coupling (ref. D).
Start-up occurs under normal conditions if the board detects the water temperature detection probe, found on the appliance, positioned in the
specific coil pit. If the probe is not connected, the absence is signalled by the red and blue LEDs flashing simultaneously, and the operation being
blocked.
The summer/winter button must be pressed for 5 seconds (ref A) to confirm the probe-free operation.
This condition will be saved by the board for all subsequent start-ups.
In any case, normal operation with temperature thresholds is restored when the probe is connected.
If the machine runs with the probe connected and the water temperature is not suitable for active operation (above 20°C in cooling and below 30°C
in heating), the ventilation will be stopped and the anomaly will be indicated by the corresponding LED of the selected function flashing (cooling
blue C or heating red D).