![Emerson unidrive m200 Скачать руководство пользователя страница 62](http://html.mh-extra.com/html/emerson/unidrive-m200/unidrive-m200_parameter-reference-manual_102553062.webp)
Menu 5 Single Line Descriptions −
Motor Control
Mode: Open
‑
loop
Parameter
Range
Default
Type
05.001 Output Frequency
±VM_SPEED_FREQ_REF Hz
RO Num ND NC PT FI
05.002 Output Voltage
±VM_AC_VOLTAGE V
RO Num ND NC PT FI
05.003 Output Power
±VM_POWER kW
RO Num ND NC PT FI
05.004 Motor Rpm
±33000 rpm
RO Num ND NC PT FI
05.005 D.c. Link Voltage
±VM_DC_VOLTAGE V
RO Num ND NC PT FI
05.006 Motor Rated Frequency
0.00 to 550.00 Hz
50Hz: 50.00 Hz
60Hz: 60.00 Hz
RW Num
US
05.007 Motor Rated Current
±VM_RATED_CURRENT A
0.00 A
RW Num RA US
05.008 Motor Rated Speed
0.0 to 33000.0 rpm
50Hz: 1500.0 rpm
60Hz: 1800.0 rpm
RW Num
US
05.009 Motor Rated Voltage
±VM_AC_VOLTAGE_SET V
110V drive: 230 V
200V drive: 230 V
400V drive 50Hz: 400 V
400V drive 60Hz: 460 V
575V drive: 575 V
690V drive: 690 V
RW Num RA US
05.010 Motor Rated Power Factor
0.00 to 1.00
0.85
RW Num RA US
05.011 Number Of Motor Poles
0 to 16 Pole pairs
0 Pole pairs
RW Num
US
05.012 Auto
‑
tune
0 to 2
0
RW Num NC
05.013 Dynamic V To F Select
0 to 1
0
RW Num
US
05.014 Open
‑
loop Voltage Mode
Ur.S (0), Ur (1), FD (2), Ur.Auto (3), Ur.I (4),
SrE (5), Fd.tap (6)
Ur.I (4)
RW Txt
US
05.015 Low Frequency Voltage Boost
0.0 to 25.0 %
3.0 %
RW Num
US
05.017 Stator Resistance
0.0000 to 99.9999 Ω
0.0000 Ω
RW Num RA US
05.018 Maximum Switching Frequency
0 to VM_MAX_SWITCHING_FREQUENCY kHz
3 (3) kHz
RW Txt
RA US
05.019 High Stability Space Vector Modulation
Off (0) or On (1)
Off (0)
RW Bit
US
05.020 Over Modulation Enable
Off (0) or On (1)
Off (0)
RW Bit
US
05.024 Transient Inductance
0.000 to 500.000 mH
0.000 mH
RW Num RA US
05.025 Stator Inductance
0.00 to 5000.00 mH
0.00 mH
RW Num RA US
05.027 Slip Compensation Level
±150.0 %
100.0 %
RW Num
US
05.028 Flux Control Compensation Disable
Off (0) or On (1)
Off (0)
RW Bit
US
05.031 Voltage Controller Gain
1 to 30
1
RW Num
US
05.032 Torque Per Amp
0.00 to 500.00 Nm/A
RO Num ND NC PT
05.033 Slip Compensation Limit
0.00 to 10.00 Hz
10.00 Hz
RW Num
US
05.035 Auto
‑
switching Frequency Change Disable
0 to 1
0
RW Num
US
05.036 Slip Compensation Filter
64 (0), 128 (1), 256 (2), 512 (3) ms
128 (1) ms
RW Txt
US
05.037 Switching Frequency
0 to VM_MAX_SWITCHING_FREQUENCY kHz
RO Txt ND NC PT
05.038 Minimum Switching Frequency
0 to VM_MAX_SWITCHING_FREQUENCY kHz
0.667 (0) kHz
RW Txt
RA US
05.040 Spin Start Boost
0.0 to 10.0
1.0
RW Num
US
05.042 Reverse Output Phase Sequence
Off (0) or On (1)
Off (0)
RW Bit
US
05.059 Maximum Deadtime Compensation
0.000 to 10.000 µs
0.000 µs
RO Num NC PT US
05.060 Current At Maximum Deadtime Compensation
0.00 to 100.00 %
0.00 %
RO Num NC PT US
05.061 Disable Deadtime Compensation
Off (0) or On (1)
Off (0)
RW Bit
US
05.074 Boost End Voltage
0.0 to 100.0 %
50.0 %
RW Num
US
05.075 Boost End Frequency
0.0 to 100.0 %
50.0 %
RW Num
US
05.076 Second Point Voltage
0.0 to 100.0 %
55.0 %
RW Num
US
05.077 Second Point Frequency
0.0 to 100.0 %
55.0 %
RW Num
US
05.078 Third point voltage
0.0 to 100.0 %
75.0 %
RW Num
US
05.079 Third point frequency
0.0 to 100.0 %
75.0 %
RW Num
US
05.080 Low acoustic noise enable
Off (0) or On (1)
Off (0)
RW Bit
US
05.081 Change to maximum drive switching frequency at low output current
Off (0) or On (1)
Off (0)
RW Bit
US
05.083 Voltage Shelving Disable
Off (0) or On (1)
Off (0)
RW Bit
US
05.084 Low Frequency Torque adjustment
0.0 to 100.0 %
0.0 %
RW Num
US
05.088 Ur Mode Pre
‑
Flux delay
0.0 to 0.7 s
0.1 s
RW Num
US
RW Read / Write
RO Read-only
Bit
Bit parameter
Txt
Text string
Date Date parameter
Time Time parameter
Chr Character parameter
Bin Binary parameter
IP
IP address
Mac MAC address
Ver
Version number
SMP Slot, menu, parameter
Num Number parameter
DE Destination
ND No default value
RA
Rating dependent
NC
Non-copyable
PT
Protected
FI
Filtered
US User save
PS
Power-down save
62
Unidrive M200 Parameter Reference Guide
Issue: 01.05.00.10
Содержание unidrive m200
Страница 1: ...Parameter Reference Guide Unidrive M200 Open loop Mode Issue 01 05 00 10 ...
Страница 29: ...Menu 2 Frequency Ramps Mode Open loop Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 29 ...
Страница 30: ...30 Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 ...
Страница 83: ...Enable logic Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 83 ...
Страница 100: ...Menu 7 Analog I O Mode Open loop 100 Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 ...
Страница 113: ...Menu 8 Digital I O Mode Open loop Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 113 ...
Страница 125: ...Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 125 ...
Страница 144: ...Menu 10 Status and Trips Mode Open loop 144 Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 ...
Страница 145: ...Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 145 ...
Страница 204: ...204 Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 ...