Parameter
10.038
User Trip
Short description
Defines which user trip is to occur
Mode
Open
‑
loop
Minimum
0
Maximum
255
Default
Units
Type
8 Bit Volatile
Update Rate
Background read
Display Format
Standard
Decimal Places
0
Coding
RW, ND, NC, BU
When a value other than zero is written to the
User Trip
(10.038) the actions described in the following table are performed. The drive immediately writes the value
back to zero. If the value is not included in the table, then the action is the same as if the trip with the same number (with sub-trip zero) occurred provided the drive is
not already tripped.
Because the drive clears this parameter to 0 immediately, the value must be written via serial communication or user program if supported.
Action
User Trip
(10.038)
No action
Numbers corresponding to
priority 1, 2 or 3 trips
Drive reset
100
Clear trip logs (
Trip 0
(10.020) to
Trip 9
(10.029),
Trip 0 Date
(10.041) to
Trip 9 Time
(10.060) and
Trip 0 Sub-trip Number
(10.070) to
Trip 9 Sub-trip Number
(10.079))
255
Parameter
10.039
Braking Resistor Thermal Accumulator
Short description
Shows the level of the braking resistor thermal accumulator
Mode
Open
‑
loop
Minimum
0.0
Maximum
100.0
Default
Units
%
Type
16 Bit Volatile
Update Rate
Background write
Display Format
Standard
Decimal Places
1
Coding
RO, ND, NC, PT
See
Braking Resistor Rated Power
(10.030).
Parameter
10.040
Status Word
Short description
Shows the status word for the drive
Mode
Open
‑
loop
Minimum
0
(Display: 000000000000000)
Maximum
32767
(Display: 111111111111111)
Default
Units
Type
16 Bit Volatile
Update Rate
Background write
Display Format
Binary
Decimal Places
0
Coding
RO, ND, NC, PT
The bits in
Status Word
(10.040) mirror the status bit parameters as shown below. Where the parameters do not exist in any mode the bit remains at zero.
Bit
Status parameter
0
Drive Healthy
(10.001)
1
Drive Active
(10.002)
2
Zero Frequency
(10.003)
3
Running At Or Below Minimum Frequency
(10.004)
4
Below Set Frequency
(10.005)
5
At Frequency
(10.006)
6
Above Set Frequency
(10.007)
7
Rated Load Reached
(10.008)
8
Current limit active
(10.009)
9
Regenerating
(10.010)
10
Braking IGBT Active
(10.011)
11
Braking Resistor Alarm
(10.012)
12
Reverse Direction Commanded
(10.013)
13
Reverse Direction Running
(10.014)
14
Supply Loss
(10.015)
Because of the limited number of segments on drives with an LED display, these drives will indicate the parameter value as a
decimal value rather than a binary value.
Parameter
10.041
Trip 0 Date
Short description
Shows the date at which trip 0 occurred
Mode
Open
‑
loop
Minimum
0
(Display: 00-00-00)
Maximum
311299
(Display: 31-12-99)
Default
Units
Type
32 Bit Power Down Save
Update Rate
Write on trip
Display Format
Date
Decimal Places
0
Coding
RO, ND, NC, PT
160
Unidrive M200 Parameter Reference Guide
Issue: 01.05.00.10
Содержание unidrive m200
Страница 1: ...Parameter Reference Guide Unidrive M200 Open loop Mode Issue 01 05 00 10 ...
Страница 29: ...Menu 2 Frequency Ramps Mode Open loop Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 29 ...
Страница 30: ...30 Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 ...
Страница 83: ...Enable logic Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 83 ...
Страница 100: ...Menu 7 Analog I O Mode Open loop 100 Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 ...
Страница 113: ...Menu 8 Digital I O Mode Open loop Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 113 ...
Страница 125: ...Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 125 ...
Страница 144: ...Menu 10 Status and Trips Mode Open loop 144 Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 ...
Страница 145: ...Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 145 ...
Страница 204: ...204 Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 ...