This is the motor map 2 equivalent for
Motor Rated Speed
(05.008).
Parameter
21.009
M2 Motor Rated Voltage
Short description
Defines the motor rated voltage used for motor map 2
Mode
Open
‑
loop
Minimum
−VM_AC_VOLTAGE_SET
Maximum
VM_AC_VOLTAGE_SET
Default
See exceptions below
Units
V
Type
16 Bit User Save
Update Rate
16ms
Display Format
Standard
Decimal Places
0
Coding
RW, VM, RA
Voltage
Region
Default Value
110V
All
230
200V
All
230
400V
50Hz
400
400V
60Hz
460
575V
All
575
690V
All
690
This is the motor map 2 equivalent for
Motor Rated Voltage
(05.009).
Parameter
21.010
M2 Motor Rated Power Factor
Short description
Defines the motor rated power factor used for motor map 2
Mode
Open
‑
loop
Minimum
0.00
Maximum
1.00
Default
0.85
Units
Type
16 Bit User Save
Update Rate
Background read/write
Display Format
Standard
Decimal Places
2
Coding
RW, RA
This is the motor map 2 equivalent for
Motor Rated Power Factor
(05.010).
Parameter
21.011
M2 Number Of Motor Poles
Short description
Defines the number of motor poles used for motor map 2
Mode
Open
‑
loop
Minimum
0
Maximum
16
Default
0
Units
Pole pairs
Type
8 Bit User Save
Update Rate
Background read
Display Format
Standard
Decimal Places
0
Coding
RW, BU
This is the motor map 2 equivalent for
Number Of Motor Poles
(05.011).
Parameter
21.012
M2 Stator Resistance
Short description
Defines the stator resistance used for motor map 2
Mode
Open
‑
loop
Minimum
0.0000
Maximum
99.9999
Default
0.0000
Units
Ω
Type
32 Bit User Save
Update Rate
Background read
Display Format
Standard
Decimal Places
4
Coding
RW, RA
This is the motor map 2 equivalent for
Stator Resistance
(05.017).
Parameter
21.014
M2 Transient Inductance
Short description
Defines the transient inductance used for motor map 2
Mode
Open
‑
loop
Minimum
0.000
Maximum
500.000
Default
0.000
Units
mH
Type
32 Bit User Save
Update Rate
Background read
Display Format
Standard
Decimal Places
3
Coding
RW, RA
This is the motor map 2 equivalent for
Transient Inductance
(05.024).
Unidrive M200 Parameter Reference Guide
Issue: 01.05.00.10
225
Содержание unidrive m200
Страница 1: ...Parameter Reference Guide Unidrive M200 Open loop Mode Issue 01 05 00 10 ...
Страница 29: ...Menu 2 Frequency Ramps Mode Open loop Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 29 ...
Страница 30: ...30 Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 ...
Страница 83: ...Enable logic Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 83 ...
Страница 100: ...Menu 7 Analog I O Mode Open loop 100 Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 ...
Страница 113: ...Menu 8 Digital I O Mode Open loop Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 113 ...
Страница 125: ...Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 125 ...
Страница 144: ...Menu 10 Status and Trips Mode Open loop 144 Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 ...
Страница 145: ...Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 145 ...
Страница 204: ...204 Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 ...