Motorised pot
If
Motorised Pot Reset
(09.028) = 1 then the motorised pot is disabled and held in its reset state with
Motorised Pot Output
(09.003) = 0.0%. If
Motorised Pot Reset
(09.028) = 0 the motorised pot is enabled even if
Motorised Pot Destination
(09.025) is not routed to a valid parameter. The
sample rate of the motorised pot is always 4ms.
When the motorised pot is active
Motorised Pot Output
(09.003) can be increased or decreased by setting
Motorised Pot Up
(09.026) or
Motorised Pot Down
(09.027) to 1 respectively. If both
Motorised Pot Up
(09.026) and
Motorised Pot Down
(09.027) are 1 then
Motorised Pot Output
(09.003) is increased. The rate of change of
Motorised Pot Output
(09.003) is defined by
Motorised Pot Rate
(09.023) which gives the time to change
from 0 to 100%. The time to change from -100% to 100% is
Motorised Pot Rate
(09.023) x 2. If
Motorised Pot Bipolar Select
(09.022) = 0 then
Motorised Pot Output
(09.003) is limited in the range 0.00% to 100.00%, otherwise it is allowed to change in the range from -100.00% to 100.00%.
Motorised Pot Mode
(09.021) defines the mode of operation as given in the table below.
Motorised Pot Mode
(09.021)
Motorised Pot Output
(09.003)
Motorised Pot Up
(09.026) and
Motorised Pot Down
(09.027) active
0
Reset to zero at power-up
Always
1
Set to power-down value at power-up
Always
2
Reset to zero at power-up
When
Drive Active
(10.002) = 1
3
Set to power-down value at power-up
When
Drive Active
(10.002) = 1
4
Reset to zero at power-up and when
Drive Active
(10.002) = 0
When
Drive Active
(10.002) = 1
Motorised Pot Scaling
(09.024) introduces a scaling factor at the output of the motorised pot before the output is routed to the destination. If
Motorised Pot Scaling
(09.024)
Motorised Pot Scaling
(09.024) > 1.000 the output will exceed the range of the destination parameter, and so the
destination parameter will be at its maximum or minimum before the output of the motorised pot reaches the limits of its range.
126
Unidrive M200 Parameter Reference Guide
Issue: 01.05.00.10
Содержание unidrive m200
Страница 1: ...Parameter Reference Guide Unidrive M200 Open loop Mode Issue 01 05 00 10 ...
Страница 29: ...Menu 2 Frequency Ramps Mode Open loop Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 29 ...
Страница 30: ...30 Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 ...
Страница 83: ...Enable logic Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 83 ...
Страница 100: ...Menu 7 Analog I O Mode Open loop 100 Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 ...
Страница 113: ...Menu 8 Digital I O Mode Open loop Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 113 ...
Страница 125: ...Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 125 ...
Страница 144: ...Menu 10 Status and Trips Mode Open loop 144 Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 ...
Страница 145: ...Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 145 ...
Страница 204: ...204 Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 ...