Parameter
04.017
Magnetising Current
Short description
Shows the instantaneous level of magnetising current
Mode
Open
‑
loop
Minimum
−VM_DRIVE_CURRENT
Maximum
VM_DRIVE_CURRENT
Default
Units
A
Type
32 Bit Volatile
Update Rate
1ms
Display Format
Standard
Decimal Places
2
Coding
RO, FI, VM, ND, NC, PT
Magnetising Current
(04.017) is the instantaneous level of magnetising current scaled so that it represents the r.m.s. level of magnetising current under
steady state conditions.
Parameter
04.018
Final Current Limit
Short description
Shows the final current limit that is applied to the torque producing current
Mode
Open
‑
loop
Minimum
−VM_TORQUE_CURRENT
Maximum
VM_TORQUE_CURRENT
Default
Units
%
Type
16 Bit Volatile
Update Rate
16ms
Display Format
Standard
Decimal Places
1
Coding
RO, VM, ND, NC, PT
Final Current Limit
(04.018) is the current limit level that is applied to the torque producing current. See
Thermal Protection Mode
(04.016).
Parameter
04.019
Motor Protection Accumulator
Short description
Shows the level of the motor protection accumulator
Mode
Open
‑
loop
Minimum
0.0
Maximum
100.0
Default
Units
%
Type
16 Bit Power Down Save
Update Rate
Background write
Display Format
Standard
Decimal Places
1
Coding
RO, ND, NC, PT
See
Motor Thermal Time Constant 1
(04.015).
Parameter
04.020
Percentage Load
Short description
Shows the level of torque producing current as a percentage of rated torque producing current for the
motor
Mode
Open
‑
loop
Minimum
−VM_USER_CURRENT
Maximum
VM_USER_CURRENT
Default
Units
%
Type
16 Bit Volatile
Update Rate
Background write
Display Format
Standard
Decimal Places
1
Coding
RO, FI, VM, ND, NC, PT
Percentage Load
(04.020) gives the
Torque Producing Current
(04.002) as a percentage of the rated torque producing current for the motor. Positive
values indicate motoring and negative values represent regenerating.
Parameter
04.024
User Current Maximum Scaling
Short description
Defines the maximum for the torque reference and percentage load parameters
Mode
Open
‑
loop
Minimum
−VM_TORQUE_CURRENT_UNIPOLAR Maximum
VM_TORQUE_CURRENT_UNIPOLAR
Default
165.0
Units
%
Type
16 Bit User Save
Update Rate
Background read
Display Format
Standard
Decimal Places
1
Coding
RW, VM, RA
User Current Maximum Scaling
(04.024) defines the variable maximum/minimums VM_USER_CURRENT which is applied to
Percentage Load
(04.020). This is useful when routing these parameters to an analogue output as it allows the full scale output value to be defined by the user.
It also defines the maximum value of
Torque Reference
(04.008) such that when torque is is being set by an analog input the maximum value set here
will be requested when the analog input is at maximum.
The maximum value (VM_TORQUE_CURRENT_UNIPOLAR [MAX]) varies between drive sizes with default parameters loaded. For some drive sizes
the default value may be reduced below the value given by the parameter range limiting.
60
Unidrive M200 Parameter Reference Guide
Issue: 01.05.00.10
Содержание unidrive m200
Страница 1: ...Parameter Reference Guide Unidrive M200 Open loop Mode Issue 01 05 00 10 ...
Страница 29: ...Menu 2 Frequency Ramps Mode Open loop Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 29 ...
Страница 30: ...30 Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 ...
Страница 83: ...Enable logic Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 83 ...
Страница 100: ...Menu 7 Analog I O Mode Open loop 100 Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 ...
Страница 113: ...Menu 8 Digital I O Mode Open loop Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 113 ...
Страница 125: ...Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 125 ...
Страница 144: ...Menu 10 Status and Trips Mode Open loop 144 Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 ...
Страница 145: ...Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 145 ...