{HF18}
Sub-trip Reason
1
Option module initialization timed out
2
Programming error while writing menu in flash
3
Erase flash block containing setup menus failed
4
Erase flash block containing application menus failed
5
Incorrect setup menu CRC contained in flash
6
Incorrect application menu CRC contained in flash
{HF19} The
HF19
trip indicates that the drive firmware is partially or completely deleted. The drive is now in its bootloader and is
waiting for a new image to be downloaded using UniMConnect. Once a new image is downloaded, the drive can run normally.
When the drive is subsequently powered up a
Stored HF
trip is initiated where the sub-trip number is the number of the HF trip that last occurred. This trip will occur at every power-
up until it is reset. The trip can only be reset by first entering 1299 into
Parameter mm.000
(mm.000). If the drive is powered up and a
Stored HF
trip occurs,
Onboard User Program: Enable
(11.047) is reset to zero to prevent the on-board user program from running. This ensures that the user program can be changed or erased in case it
causes an HF trip at every power-up.
Trip descriptions
Trips shown in the table below can be generated either from the drive control system or from the power system. The sub-trip number which is in the form xxyzz is used to identify the
source of the trip. The digits xx are 00 for a trip generated by the control system or the number of a power module if generated by the power system. If the drive is not a multi-power
module drive then xx will always have a value of 1 if the trip is related to the power system. The y digit is used to identify the location of a trip which is generated by a rectifier module
connected to a power module. Where the y digit is relevant it will have a value of 1 or more, otherwise it will be 0. The zz digits give the reason for the trip and are defined in each trip
description.
Over Volts
OHt dc bus
OI ac
Phase Loss
OI Brake
LF Power Comms
PSU
OI Snubber
OHt Inverter
Temp Feedback
OHt Power
Power Data
Trips Summary
(numerical order)
244
Unidrive M200 Parameter Reference Guide
Issue: 01.05.00.10
Содержание unidrive m200
Страница 1: ...Parameter Reference Guide Unidrive M200 Open loop Mode Issue 01 05 00 10 ...
Страница 29: ...Menu 2 Frequency Ramps Mode Open loop Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 29 ...
Страница 30: ...30 Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 ...
Страница 83: ...Enable logic Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 83 ...
Страница 100: ...Menu 7 Analog I O Mode Open loop 100 Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 ...
Страница 113: ...Menu 8 Digital I O Mode Open loop Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 113 ...
Страница 125: ...Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 125 ...
Страница 144: ...Menu 10 Status and Trips Mode Open loop 144 Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 ...
Страница 145: ...Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 145 ...
Страница 204: ...204 Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 ...