time period that spans the ends of the repeat period as shown in the example above. It should be noted that if this method is used to allow the active
period to span the ends of the repeat period then if the timer is disabled the output of the timer block before the invert becomes 0, and so the final
output of the timer after the invert is 1.
See
User Functions 1
for more information.
Parameter
09.042
Timer 1 Output
Short description
Shows the output state of timer function 1
Mode
Open
‑
loop
Minimum
0
Maximum
1
Default
Units
Type
1 Bit Volatile
Update Rate
Background write
Display Format
Standard
Decimal Places
0
Coding
RO, ND, NC, PT
Timer 1 Output
(09.042) shows the output of the timer function 1.
Parameter
09.043
Timer 1 Destination
Short description
Defines the output destination of timer function 1
Mode
Open
‑
loop
Minimum
0.000
Maximum
30.999
Default
0.000
Units
Type
16 Bit User Save
Update Rate
Drive reset read
Display Format
Standard
Decimal Places
3
Coding
RW, DE, PT, BU
Timer 1 Destination
(09.043) defines the output destination of timer function 1.
Parameter
09.045
Timer 2 Start Date
Short description
Defines the start date for timer 2
Mode
Open
‑
loop
Minimum
0
(Display: 00-00-00)
Maximum
311299
(Display: 31-12-99)
Default
0
(Display: 00-00-00)
Units
Type
32 Bit User Save
Update Rate
Background read
Display Format
Date
Decimal Places
0
Coding
RW
Timer 2 Start Date
(09.045) defines the start date within the repeat period of timer 2.
See
Timer 1 Repeat Function
(09.039) for more information.
Parameter
09.046
Timer 2 Start Time
Short description
Defines the start time for timer 2
Mode
Open
‑
loop
Minimum
0
(Display: 00:00:00)
Maximum
235959
(Display: 23:59:59)
Default
0
(Display: 00:00:00)
Units
Type
32 Bit User Save
Update Rate
Background read
Display Format
Time
Decimal Places
0
Coding
RW
Timer 2 Start Time
(09.046) defines the start time within the repeat period of timer 2.
See
Timer 1 Repeat Function
(09.039) for more information.
Parameter
09.047
Timer 2 Stop Date
Short description
Mode
Open
‑
loop
Minimum
0
(Display: 00-00-00)
Maximum
311299
(Display: 31-12-99)
Default
0
(Display: 00-00-00)
Units
Type
32 Bit User Save
Update Rate
Background read
Display Format
Date
Decimal Places
0
Coding
RW
Timer 2 Stop Date
(09.047) defines the stop date within the repeat period of timer 2.
See
Timer 1 Repeat Function
(09.039) for more information.
138
Unidrive M200 Parameter Reference Guide
Issue: 01.05.00.10
Содержание unidrive m200
Страница 1: ...Parameter Reference Guide Unidrive M200 Open loop Mode Issue 01 05 00 10 ...
Страница 29: ...Menu 2 Frequency Ramps Mode Open loop Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 29 ...
Страница 30: ...30 Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 ...
Страница 83: ...Enable logic Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 83 ...
Страница 100: ...Menu 7 Analog I O Mode Open loop 100 Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 ...
Страница 113: ...Menu 8 Digital I O Mode Open loop Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 113 ...
Страница 125: ...Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 125 ...
Страница 144: ...Menu 10 Status and Trips Mode Open loop 144 Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 ...
Страница 145: ...Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 145 ...
Страница 204: ...204 Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 ...