Priority Category
Trips
Comments
1
Internal faults
HF01 - HF19
These are fatal problems that cannot be reset. All drive features are inactive after any of these trips occur. If a basic
keypad is fitted it will show the trip, but the keypad will not function. These trips are not stored in the trip log.
1
Stored HF trip
Stored HF
This trip cannot be cleared unless 1299 is entered into
Parameter mm.000
(mm.000) and a reset is initiated.
2
Non-resettable trips
Trip numbers
218 - 247 and
Slot1 HF
These trips cannot be reset.
3
Volatile memory
failure
EEPROM Fail
This can only be reset if
Parameter mm.000
(mm.000) is set to 1233 or 1244, or if
Load Defaults
(11.043) is set to
a non-zero value
4
Non-volatile media
trips
Trip numbers
174, 175 and
177 - 188
These trips are priority 5 during power-up
5
Trips with extended
reset times
OI ac
and
OI Brake
These trips cannot be reset until 10s after the trip was initiated.
5
Phase loss and d.c.
link power circuit
protection
Phase Loss
and
OHt dc bus
The drive will attempt to stop the motor before tripping if a
Phase Loss
.000 trip occurs unless this feature has been
disabled (see
Action On Trip Detection
(10.037)). The drive will always attempt to stop the motor before tripping if
an
OHt dc bus
occurs.
5
Standard trips
All other trips
Trips {HF01} to {HF19} are internal faults that do not have trip numbers. If one of these trips occurs, the main drive processor has detected an irrecoverable error. All
drive functions are stopped and the trip message will be displayed on the drive keypad. The error can only be reset by powering the drive down and up again. The
table below gives the reasons for internal faults and their corresponding trip
154
Unidrive M200 Parameter Reference Guide
Issue: 01.05.00.10
Содержание unidrive m200
Страница 1: ...Parameter Reference Guide Unidrive M200 Open loop Mode Issue 01 05 00 10 ...
Страница 29: ...Menu 2 Frequency Ramps Mode Open loop Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 29 ...
Страница 30: ...30 Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 ...
Страница 83: ...Enable logic Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 83 ...
Страница 100: ...Menu 7 Analog I O Mode Open loop 100 Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 ...
Страница 113: ...Menu 8 Digital I O Mode Open loop Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 113 ...
Страница 125: ...Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 125 ...
Страница 144: ...Menu 10 Status and Trips Mode Open loop 144 Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 ...
Страница 145: ...Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 145 ...
Страница 204: ...204 Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 ...