Instruction Manual
IM-106-880C, OI
Section 7: Foundation
Fieldbus
April 2017
Alarm
Detection
13
9
7.12.7
Alarm Detection
A block alarm will be generated whenever the BLOCK_ERR has an error bit set. The types of block
error for the AI block are defined above.
Process alarm detection is based on the PV value. You can configure the alarm limits of the
following standard alarms:
•
High (HI_LIM)
•
High high (HI_HI_LIM)
•
Low (LO_LIM)
•
Low low (LO_LO_LIM)
Additional process alarm detection is based on the difference between SP and PV values and can
be configured via the following parameters:
•
Deviation high (DV_HI_LIM)
•
Deviation low (DV_LO_LIM)
In order to avoid alarm chattering when the variable is oscillating around the alarm limit, an
alarm hysteresis in percent of the PV span can be set using the ALARM_HYS parameter. The
priority of each alarm is set in the following parameters:
•
HI_PRI
•
HI_HI_PRI
•
LO_PRI
•
LO_LO_PRI
•
DV_HI_PRI
•
DV_LO_PRI
Alarms are grouped into five levels of priority:
Table 7-29 Alarm priority levels
Priority Number
Priority Description
0
The priority of an alarm condition changes to after the condition that caused the alarm is corrected.
1
An alarm condition with a priority of 1 is recognized by the system, but is not reported to the
operator.
2
An alarm condition with a priority of 2 is reported to the operator, but does not require operator
attention (such as diagnostics and system alerts).
3-7
Alarm conditions of priority 3 to 7 are advisory alarms of increasing priority.
10-15
Alarm conditions of priority 8 to 15 are critical alarms of increasing priority.
Содержание Rosemount OCX 8800
Страница 2: ......
Страница 41: ...Instruction Manual IM 106 880C OI Section 2 Installation April 2017 Section contents 17 ...
Страница 192: ...Section 7 Foundation Fieldbus April 2017 Instruction Manual IM 106 880C OI 16 6 About AMS and DeltaV Software ...
Страница 205: ...Alarm Relay Events April 2017 Instruction Manual IM 106 880C OI 17 8 Alarm Relay Events ...
Страница 251: ...Replace Tube Fittings April 2017 Instruction Manual IM 106 880C OI 22 4 Install Tube Fittings ...
Страница 259: ...Section 10 Replacement Parts April 2017 Instruction Manual IM 106 880C OI 23 2 O2 Cell and Heater Strut Assembly ...
Страница 261: ...Instruction Manual IM 106 880C OI Safety Data April 2017 Appendix contents 233 ...
Страница 263: ...Instruction Manual Safety Data IM 106 880C OI April 2017 Safety Instructions 235 ...
Страница 267: ...Instruction Manual Safety Data IM 106 880C OI April 2017 Safety Instructions 239 ...
Страница 271: ...Instruction Manual Safety Data IM 106 880C OI April 2017 Safety Instructions 243 ...
Страница 273: ...Instruction Manual Safety Data IM 106 880C OI April 2017 Safety Instructions 245 ...
Страница 275: ...Instruction Manual Safety Data IM 106 880C OI April 2017 IMPORTANT Safety Instructions 247 ...
Страница 277: ...Instruction Manual Safety Data IM 106 880C OI April 2017 Safety Instructions 249 ...
Страница 279: ...Instruction Manual Safety Data IM 106 880C OI April 2017 Safety Instructions 251 ...
Страница 298: ...SPA with HART Alarm April 2017 Instruction Manual IM 106 880C OI 27 2 Configuration Calibratio n ...
Страница 300: ...Instruction Manual IM 106 880C OI Index April 2017 Manual index 27 4 ...
Страница 304: ...Index April 2017 Instruction Manual IM 106 880C OI 27 8 Manual index ...
Страница 305: ......