background image

 

 

Operating instruction 

Pressure Transmitter PT5N-…-FLR  

for flammable refrigerants 

 

 

 

Emerson Climate Technologies GmbH  

www.climate.emerson.com/en-gb

 

Am Borsigturm 31 I 13507 Berlin I Germany 

Date: 13.09.2019   

PT5N-FLR_OI_ML_R05_866913.docx 

G e n e r a l   I nf o r ma t i o n :  

The pressure transmitter PT5N-…P-FLR consists of a 

hybrid film stainless steel measuring cell with a 

diaphragm, installed in a stainless-steel housing. The 

pressure measuring cell is fully welded. The pressure 

transmitter is intended for use in flammable refrigerants 

operated air conditioning and refrigeration systems as 

well as heat pumps and it converts a pressure into a 

linear electrical output signal. 

PT5N-…P-FLR is preset to the specific measuring 

range at the manufactures plant. An additional setting 

is not possible. The pressure transmitter can only be 

used in hazardous area defined by zone 2 (category 3).  

  S a f e ty   i n s tr u c t i o n s : 

 

The device may only be used for the purposes 

specified in these instructions.  

 

If the device is not used properly, serious bodily 

injury and/or considerable damage to property 

cannot be excluded. This should be kept in mind 

particularly when the device was in use and is 

replaced. 

 

The installation, mounting and commissioning of 

the 

  devices should be performed only by 

trained personnel and should comply with the 

standard EN 60079-14. 

 

Flammable refrigerants require special handling 

and care due to its flammability. Sufficient 

ventilation is required during service of the 

system. Contact with rapidly expanding gases can 

cause frostbite and eye damage. Proper protective 

equipment (gloves, eye protection, etc.) has to be 

used. 

 

Ensure that the system is correctly labeled with 

applied refrigerant type and a warning for 

explosion risk. 

 

Do not release any refrigerant into the 

atmosphere! 

 

Do not exceed the specified maximum ratings for 

pressure, temperature, voltage and current. 

 

Before opening any system make sure pressure in 

system is brought to and remains at atmospheric 

pressure. 

 

Before installation or service disconnect all 

voltages from system and device. 

 

Observe and avoid mechanical damage of housing 

in order to maintain protection class. 

 

Ensure that design, installation and operation are 

according to European and national 

standards/regulations. 

I n s t a l l a t i o n   ( F i g .   1 ) :  

 

Before installation compare the controller data with 

the data of the name plate.  

 

The effects of UV radiation can cause materials to 

become brittle. Protect the device from direct 

sunlight. 

 

Mounting directions per Fig.1 in order to prevent the 

collection of contaminant in pressure sensing 

element. 

B r a z i ng   ( F i g .   2 ) : 

 

Perform and consider the brazing joint as per 

EN 14324. 

 

Before and after brazing clean tubing and brazing 

joints. 

 

Minimize vibrations in the piping lines by 

appropriate solutions. 

 

Use of flux and silver rod having a minimum of 30% 

silver. 

 

Do not exceed the max. body temperature of 

120°C!

 

P r e s s ur e   t e s t :  

After completion of installation, a pressure test must be 

carried out according to EN 378 for systems which 

must comply with European pressure equipment 

directive 2014/68/EU. 

 Warning: 

 

Failure to do so could result in loss of refrigerant 

and personal injury. 

 

The pressure test must be conducted by skilled 

persons with due respect regarding the danger 

related to pressure

T i g h t n e s s   t e s t : 

Conduct Tightness test according EN378-2 with 

appropriate equipment and method to identify tightness 

of external joints. The allowable leakage rate must be 

according system manufacturer’s specification. 

  E l e c t r i c a l   c o n n e c ti o n : 

 

Entire electrical connections have to comply with 

local regulations. 

 

Ensure that the system piping is grounded (Fig.3) 

so housing of pressure transmitter has connection 

to ground via brazed connection.

 

Note: 

It is mandatory the electrical connection of 

pressure transmitter housing to the ground 

(grounding). If the connection is not 

arranged/established via connection to grounded 

piping system, it is necessary the electrical 

connection via plug and cable assembly. It is required 

an ATEX certified M12 plug and cable assembly 

having 3 wires (2 wires for signal output and 1 wire 

for grounding)

.

 

 

Connect the device to a low voltage power supply 

with safe separation (SELV). 

 

The device should only be supplied with limited 

energy according to UL 61010-1 Second Edition, 

Section 9.3 or LPS in conformance with UL 60950-1 

or class 2 in compliance with UL 1310 or UL 1585. 

 

Use only prewired M12 Connector PT4-M60-FLR 

for connection to the pressure transmitter. PT4-M60-

FLR can be used in zone 2 (category 3). 

 

During operation, the connector PT4-M60-FLR must 

be  protected by an appropriate housing against 

external mechanical damage or shock (min. required 

protection up to a mechanical action of 7 J  -  in 

accordance with EN60079-0)  

 

Cable end of PT4-M60-FLR must be connected to a 

driver/controller in compliance with applicable 

directives/standards for installation in hazardous 

location. 

-

 

If driver/controller is located out of hazard zone, 

appropriate ATEX approved cable gland shall be 

used in boundary of hazard zone and out of hazard 

zone. 

-

 

Applicable Driver/controller must contain 

istrincally-safe 

resistive

  circuit  and insured 

maximum supply voltage below 30VDC and 

maximum current below 100 mA. 

-

 

If the cable needs to be extended (maximum total 

length 6 m) in hazard zone, it is mandatory to use 

ATEX approved type coupling or junction box.  

Wiring and mounting of plug PT4-M60-FLR:  

 

Do not bend or mechanically stress the cable outlet, 

maintain a clearance of 20 mm to neighboring parts. 

 

Ensure that the cables are mounted without tension; 

always leave the cable a bit loose, but fixed.  

 

Ensure that cables are not mounted near sharp edges.  

 

Prewired plug and cable assembly

 

is ready for 

connection to the Pressure transmitter.  

 

Allow enough space on top of pressure transmitter to 

mount plug as shown in Fig.5. The plug can be 

mounted on pressure transmitter only in one position 

(Fig.4 marking: 

). 

 

 

Prewired plug and cable assembly is ready for 

connection to the transmitter.

 

1.

 

Push the plug on pins on top of the pressure 

transmitter. (Fig.4) 

2.

 

Rotate the nut one turn in clockwise direction and 

push the plug. 

3.

 

Repeat this procedure until the plug is tightened. 

 

Disconnection of electrical plug from device only 

when the power is switched off. 

 

Ensure polarity for connection of 2-wire cable to 

controller:  

-

 

+24V DC to be connected to brown wire  

-

 

Output Signal / 0V to be connected to white wire 

 

  O p e r a t i o n : 

 

Perform a functional test of electrical circuit 

before charging the system with refrigerant. 

  S e r v i c e   /   Ma i n t e na n c e : 

 

The transmitter is maintenance-free. Defective 

PT5N-…P-FLR must be replaced; they cannot be 

repaired. 

 

Disconnect electrical power before service. 

 

Before any debrazing ensure that the flammable 

refrigerant is pumped out of the system and the 

room around the system is well vented so no 

refrigerant left. 

T e c h ni c a l   d a ta   o f   P T 5 N - … P - F L R : 

Supply voltage 

10...30VDC, class III 

Output signal 

4…20 mA 

Instrincally-safe 

resistive circuit 

Ui ≤ 30 V

 

Ii ≤ 100 mA

,  

Pi ≤ 750 mA

 

internal inductance Li = 0 nH 

internal capacitance Ci = 0 nF 

Protection class  

(EN 60529) 

IP67 (PT4-M60-FLR) 

Medium temperature 

-30…+120°C 

Ambient temperature 

-25…+85°C 

Released/compatible  

for 

All flammable refrigerants of 

A3 group; mineral-, alkyl 

benzene and ester lubricants 

Marking  
 

  2014/34/EU 

 

 

II 3 G   

 

 

Ex ec IIC T4 Gc

 

Date of manufacture visible on label 

 

YYMMDD-XXX-XX-XXXX 

Date (year-month-day) 
3 digits of the order number 
Order position 
Single part number 

 

Only PT5N-…P-FLR types / PT4-M60-FLR, listed 

in the following table, are released for use with 

flammable refrigerants!  

Type                       

Sensing 

pressure 

range 

Max. 

standstill. 

Pressure 

Part No. 

PT5N-07P-FLR  -0.8…7 bar 

27 bar 

805390/M 

PT5N-10P-FLR  -0.8…10 bar  27 bar 

805391/M 

PT5N-30P-FLR 

0…30 bar 

60 bar 

805389/M 

Type                       

Description 

Part No. 

PT4-M60-FLR 

6.0 m cable length,  

2-wire, ATEX certified 

804806

 

 

 

 

!

!

!

!

!

Содержание PT5N FLR Series

Страница 1: ...to the ground grounding If the connection is not arranged established via connection to grounded piping system it is necessary the electrical connection via plug and cable assembly It is required an ATEX certified M12 plug and cable assembly having 3 wires 2 wires for signal output and 1 wire for grounding Connect the device to a low voltage power supply with safe separation SELV The device should...

Страница 2: ...dung ist zwingend erforderlich Wird die Verbindung nicht über den Anschluss an ein geerdetes Rohrleitungssystem hergestellt ist die elektrische Verbindung über den Stecker und Kabel erforderlich Es wird ein ATEX zertifizierter M12 Stecker mit 3 Leitern 2 Leiter für den Signalausgang und 1 Leiter für die Erdung benötigt Schließen Sie das Gerät an eine Kleinspannungs versorgung mit sicherer Trennung...

Страница 3: ...rre n est pas établie au travers de la tuyauterie du système il est nécessaire de la réaliser au travers du connecteur électrique du capteur Cela nécessite l utilisation d un connecteur M12 certifié ATEX muni d un câble à 3 fils deux pour le signal et un pour le raccordement à la terre Raccordez le transmetteur à une alimentation basse tension avec une isolation sûre SELV L appareil ne doit être a...

Страница 4: ...laciones locales Asegurar que la instalación de tuberías está conectada a tierra Fig 3 para que el transmisor lo esté asimismo vía conexión soldada Nota Es obligatorio conectar a tierra el cuerpo del transductor de presión Si el sistema de tuberías no está conectado a tierra es preciso hacerlo vía el cableado del transductor Se requiere un conjunto conector M12 con certificación ATEX y cable tripo...

Страница 5: ...ne brasata Nota è obbligatorio il collegamento elettrico verso terra dell involucro del trasmettitore di pressione messa a terra Se il collegamento non viene fatto mediante la linea di messa a terra è necessario collegare elettricamente l assieme spina cavo E necessario utilizzare un assieme spina cavo M12 certificato ATEX con 3 conduttori 2 conduttori per il segnale di uscita e 1 conduttore per l...

Страница 6: ...млен Рис 3 и корпус датчика имеет соединение с массой через паяное соединение Внимание обязательно электрическое соединение корпуса датчика давления с землей заземление Если заземление посредством соединения с заземленным трубопроводом отсутствует невозможно то необходимо заземлиться с помощью разъема и кабеля в сборе Для этого требуется сертифицированный ATEX разъем M12 с кабелем имеющий 3 провод...

Страница 7: ...Technologies GmbH www climate emerson com en gb Am Borsigturm 31 I 13507 Berlin I Germany Date 13 09 2019 PT5N FLR_OI_ML_R05_866913 docx Fig Pис 1 Fig Pис 2 Fig Pис 3 Fig Pис 4 Fig Pис 5 PT M60 FLR Fig Pис 6 mm мм PT5N xxP FLR ...

Страница 8: ...ept Non sparking Ex ec Gas Group IIC Hydrogen Protection level Gc Standard Applied harmonized standards EN 60079 0 2012 A11 2013 Explosive atmospheres Part 0 Equipment General requirements EN 60079 0 2014 Explosive atmospheres Part 0 Equipment General requirements DIN EN 60079 7 2016 Explosive atmospheres Part 7 Equipment protection by intrinsic safety e EN 60079 26 2015 Explosive atmospheres Part...

Отзывы: