Section 7: Foundation
Fieldbus
April 2017
Instruction Manual
IM-106-880C, OI
14
8
Troubleshootin
g
7.12.13
Troubleshooting
Refer to
to troubleshoot any problems that you encounter.
Table 7-30 Troubleshooting
Mode will not leave
OOS
1.
Target mode not set
2.
Configuration error
3.
Resource block
1.
Set target mode to something other than OOS.
2.
BLOCK_ERR will show the configuration error bit set. The
following are parameters that must be set before the block is
allowed out of OOS:
a.
BYPASS must be off or on and cannot be left at initial value of 0.
b.
OUT_HI_LIM must be less than or equal to OUT_LO_LIM.
c.
SP_HI_LIM must be less than or equal to SP_LO_LIM.
3.
The actual mode of the Resource block is OOS. See Resource
Block Diagnostics for corrective action.
4.
Block is not scheduled and therefore cannot execute to go to
Target Mode. Schedule the block to execute.
Mode will not leave
IMAN
4. Schedule
1.
Back Calculation
1. BKCAL_IN
a.
The link is not configured (the status would show “Not
Connected”).Configure the BKCAL_IN link to the downstream
block.
b.
The downstream block is sending back a Quality of “Bad” or a
Status of “Not Invited”. See the appropriate downstream block
diagnostics for corrective action.
Mode will not change
to
AUTO
Mode will not change
to CAS
1.
Target mode not set
2.
Input
1.
Target mode not set
2.
Cascade Input
1.
Set target mode to something other than OOS.
2.
IN
a.
The link is not configured (the status would show “Not
Connected”). Configure the IN link to the block.
b.
The upstream block is sending back a Quality of “Bad” or a Status
of “Not Invited”. Seethe appropriate upstream blockdiagnosticsfor
corrective action.
1.
Set target mode to something other than OOS.
2.
CAS_IN
a.
The link is not configured (the status would show “Not
Connected”). Configure the CAS_IN link to the block.
b.
The upstream block is sending back a Quality of “Bad” or a Status
of “Not Invited”. See the appropriate up stream block diagnostics
for corrective action.
Symptom
Possible Causes
Corrective Action
Содержание Rosemount OCX 8800
Страница 2: ......
Страница 41: ...Instruction Manual IM 106 880C OI Section 2 Installation April 2017 Section contents 17 ...
Страница 192: ...Section 7 Foundation Fieldbus April 2017 Instruction Manual IM 106 880C OI 16 6 About AMS and DeltaV Software ...
Страница 205: ...Alarm Relay Events April 2017 Instruction Manual IM 106 880C OI 17 8 Alarm Relay Events ...
Страница 251: ...Replace Tube Fittings April 2017 Instruction Manual IM 106 880C OI 22 4 Install Tube Fittings ...
Страница 259: ...Section 10 Replacement Parts April 2017 Instruction Manual IM 106 880C OI 23 2 O2 Cell and Heater Strut Assembly ...
Страница 261: ...Instruction Manual IM 106 880C OI Safety Data April 2017 Appendix contents 233 ...
Страница 263: ...Instruction Manual Safety Data IM 106 880C OI April 2017 Safety Instructions 235 ...
Страница 267: ...Instruction Manual Safety Data IM 106 880C OI April 2017 Safety Instructions 239 ...
Страница 271: ...Instruction Manual Safety Data IM 106 880C OI April 2017 Safety Instructions 243 ...
Страница 273: ...Instruction Manual Safety Data IM 106 880C OI April 2017 Safety Instructions 245 ...
Страница 275: ...Instruction Manual Safety Data IM 106 880C OI April 2017 IMPORTANT Safety Instructions 247 ...
Страница 277: ...Instruction Manual Safety Data IM 106 880C OI April 2017 Safety Instructions 249 ...
Страница 279: ...Instruction Manual Safety Data IM 106 880C OI April 2017 Safety Instructions 251 ...
Страница 298: ...SPA with HART Alarm April 2017 Instruction Manual IM 106 880C OI 27 2 Configuration Calibratio n ...
Страница 300: ...Instruction Manual IM 106 880C OI Index April 2017 Manual index 27 4 ...
Страница 304: ...Index April 2017 Instruction Manual IM 106 880C OI 27 8 Manual index ...
Страница 305: ......