4.1.7
Non-zero based lower range value(balanced system with
transmitter below seals)
Figure 4-7: Remote Capillary
L
max
108 in.
SG = 0.75
P
L
min
0 in.
d = 60 in.
H
d = 180 in.
(60 +120)
L
SG = 0.934
F
d
H
=
vertical distance from transmitter to high pressure seal
d
L
=
vertical distance from transmitter to low pressure seal
L
max
=
the maximum level of process above the high pressure seal and typically the 20
mA lower range value
L
min
=
the minimum level of process above the high pressure seal and typically the 4 mA
lower range value
SG
F
=
specific gravity of fill fluid
SG
P
=
specific gravity of process fluid
Tank span
= L
max
×
SG
= 108 in.
×
0.75 = 81 inH
2
O
4 mA
= L
min
×
SG
P
– (d
L
×
SG
F
) +(d
H
×
SG
F
)
= (0 in.
×
0.75) – (180 in.
×
0.934) + (60 in.
×
0.934) = –112.08 inH
2
O
20 mA
= L
max
×
SG
P
– (d
L
×
SG
F
) +(d
H
×
SG
F
)
= (108 in.
×
0.75) – (180 in.
×
0.934) + (60 in.
×
0.934) = –31.08 inH
2
O
Span
= 81 inH
2
O (–112.08 to –31.08 inH
2
O)
Note
Silicone 200 has a specific gravity of 0.934.
Note
The transmitter location in a closed tank does not effect the 4 mA and 20 mA set points as
shown in example A, B, and C.
Reference Manual
Configuration
00809-0100-4002
May 2020
Rosemount DP Level
81
Содержание Rosemount 1199
Страница 4: ...4 ...
Страница 8: ...Introduction Reference Manual May 2020 00809 0100 4002 8 Rosemount DP Level ...
Страница 22: ...Remote Seal Systems Reference Manual May 2020 00809 0100 4002 22 Rosemount DP Level ...
Страница 74: ...Installation Reference Manual May 2020 00809 0100 4002 74 Rosemount DP Level ...
Страница 92: ...Fill Fluids Reference Manual May 2020 00809 0100 4002 92 Rosemount DP Level ...
Страница 96: ...Maintenance and Troubleshooting Reference Manual May 2020 00809 0100 4002 96 Rosemount DP Level ...