3.18
EES hygienic flanged tank spud extended seal
Figure 3-25: EES Hygienic Flanged Tank Spud Extended Seal
A
B
A. Connection to transmitter
B. Diaphragm
3.18.1
Parts required for installation
The parts required to install the EES hygienic flanged tank spud extended seal will be
defined here. Prior to installation, you will need the following:
•
Torque wrench
•
Mounting hardware (end-user-supplied)
•
O-ring (Emerson-supplied)
Cutting and welding equipment required if installing a new tank spud.
Verify the O-ring material is appropriate for the application.
Inspect bolts to ensure the material is compatible with industry standards per the
application such as ASME PCC-1.
3.18.2
Installation steps
Follow these steps to install the EES hygienic flanged tank spud extended seal:
Procedure
2. Weld the tank spud onto the tank per plant procedures, see
. Ensure the
tank spud is not assembled to the pressure transmitter and/or the remote seal prior
to welding.
3. Remove the protective cover from the diaphragm of the remote seal. Use extreme
caution during installation to ensure the diaphragm is not damaged.
4. Insert end-user-supplied bolts in the bottom two bolt holes of the flange on the
remote seal.
5. Place the Emerson-supplied O-ring onto the groove.
Installation
Reference Manual
May 2020
00809-0100-4002
56
Rosemount DP Level
Содержание Rosemount 1199
Страница 4: ...4 ...
Страница 8: ...Introduction Reference Manual May 2020 00809 0100 4002 8 Rosemount DP Level ...
Страница 22: ...Remote Seal Systems Reference Manual May 2020 00809 0100 4002 22 Rosemount DP Level ...
Страница 74: ...Installation Reference Manual May 2020 00809 0100 4002 74 Rosemount DP Level ...
Страница 92: ...Fill Fluids Reference Manual May 2020 00809 0100 4002 92 Rosemount DP Level ...
Страница 96: ...Maintenance and Troubleshooting Reference Manual May 2020 00809 0100 4002 96 Rosemount DP Level ...