Note
Depending on the HART device (Field Communicator/AMS Wireless Configurator) DD the
following steps may be slightly different.
For the Rosemount 3051S, in the HART menu tree, go to the
Scaled variable Config
(under
guided set up). Follow the steps below: Bold text indicates entered value.
Procedure
1. Enter SV unit: (enter)
inH
2
O
2. Select Scaled data option: (select)
Linear
3. Enter Pressure value position 1: (enter)
-112.08
4. Enter Scaled Variable position 1: (enter)
0
5. Enter Pressure value position 2: (enter)
–31.08
6. Enter Scaled Variable position 2: (enter)
81
7. Enter Linear Offset: (enter)
0.00
8. Go to
Display
(under manual setup).
9. Pressure:
OFF
10. Scaled Variable:
ON
11. Module Temperature:
OFF
12. Percent of range:
OFF
Note
The transmitter is ranged –112.08 to –31.08 inH
2
O, but the display will show 0
inH
2
O at (4 mA) and 81 inH
2
O at (20 mA).
Configuration
Reference Manual
May 2020
00809-0100-4002
88
Rosemount DP Level