Note
Fill fluids can operate at lower temperatures than their shaded section shown in
For exact minimum operating temperatures, consult the Rosemount DP Level Fill Fluid
Specifications
.
Figure 5-2: Vapor Pressure Curves of General Use Fill Fluids
5.3.2
Fill fluid selection example
In an application that has a maximum process temperature of 284 °F (140 °C) and a
maximum pressure of 700 Torr, SYLTHERM
™
XLT would be recommended. However, say
the process pressure drops to 200 Torr and 284 °F (140 °C) at one point during the process
cycle, then Silicone 200 for vacuum applications would be recommended because it is the
fill fluid farthest to the right that the process falls into.
5.3.3
Fill fluid specifications
Rosemount fill fluid properties, vapor pressure curves, and specifications can be found in
the Rosemount DP Level Fill Fluid Specifications
.
Reference Manual
Fill Fluids
00809-0100-4002
May 2020
Rosemount DP Level
91