Note
EHEDG requirement on T-stub installations: the length (L) divided by the diameter
(D) of the tee is to be less than 1 (i.e. L /D < 1).
D
L
3.21
SHP hygienic Cherry-Burrell
®
“I” line seal
Figure 3-28: SHP Cherry-Burrell “I” Line Seal
A
B
A. Connection to transmitter
B. Diaphragm
3.21.1
Parts required for installation
The parts required to install the SHP Cherry-Burrell seal will be defined here. Prior to
installation, you will need the following:
•
Clamp (end-user-supplied)
•
Gasket (end-user-supplied)
•
Wrench (optional, depending on clamp)
Verify the gasket material is appropriate for the application.
3.21.2
Installation steps
Follow these steps to install the SHP Cherry-Burrell seal:
Installation
Reference Manual
May 2020
00809-0100-4002
60
Rosemount DP Level