66
MCi210 User Guide
Issue Number: 2
This parameter specifies the Modbus register addressing mode.
This parameter specifies an IP Address for a priority connection.
This parameter specifies an IP Address for a priority connection.
S.15.013
Modbus register addressing mode
Minimum
0
Maximum
1
Default
0
Units
Type
8 Bit User Save
Update Rate
Read on module reset,
Modbus interface reset
or Modbus interface
enable
Display Format
None
Decimal Places
0
Coding
RW, Txt, BU
Value
Text
Description
0
Standard
(mm x 100) + ppp - mm<=162 and ppp<=99
1
Modified
(mm x 256) + ppp - mm<=63 and ppp<=255
S.15.020
Priority connection 1
Minimum
0 (Display: 0.0.0.0)
Maximum
4294967295
(Display: 255.255.255.255)
Default
0 (Display: 0.0.0.0)
Units
Type
32 Bit User Save
Update Rate
Read on module reset,
Modbus interface reset or
Modbus interface enable
Display Format
IP Address
Decimal Places
0
Coding
RW, BU
S.15.021
Priority connection 2
Minimum
0 (Display: 0.0.0.0)
Maximum
4294967295
(Display: 255.255.255.255)
Default
0 (Display: 0.0.0.0)
Units
Type
32 Bit User Save
Update Rate
Read on module reset,
Modbus interface reset or
Modbus interface enable
Display Format
IP Address
Decimal Places
0
Coding
RW, BU