FloBoss 107 Instruction Manual
1-8
General Information
Revised June-2017
1.3.5
Battery and Super-capacitor
A super capacitor (“super-cap”) and a coin type battery work together to
provide backup power for the static RAM and the real-time clock. This
helps to ensure retention of short and longer-term data, configuration, and
operational integrity when the FB107 is not in service or is in storage.
For information on replacing the battery, refer to
Section 2.5.1
,
Removing
and Installing the Battery
.
Note:
The super-cap is
not
field-replaceable.
1.3.6
Built-in Inputs and Outputs
The built-in inputs and outputs (I/O) on the CPU consist of a 3- or 4-wire
100-ohm resistance thermal detector (RTD) input interface and five
diagnostic analog inputs (AI) that monitor the:
Logical voltage.
Battery voltage from the backplane voltage input connector.
Charge in voltage originating from the CPU power input.
System milliamps originating from the power input from the CPU.
Board temperature originating at the CPU.
1.3.7
Built-in Communications
The FB107 supports up to four communication ports. The base CPU has
three built-in communication ports:
Local Operator Interface (RS-232C) – LOI for asynchronous serial
communication (Local Port).
EIA-485 (RS-485) – COM1 for asynchronous serial communication.
EIA-232 (RS-232) – COM2 for serial communication.
Local Operator
Interface Port
The Local Operator Interface (LOI) port provides for a direct, local
link between the FB107 and a personal computer (PC) through an
optional Local Operator Interface Cable using EIA-232 (RS-232C)
communications.
The LOI local port allows you to access the FB107 for configuration and
transfer of stored data. The LOI port is capable of initiating a message in
support of Spontaneous-Report-by-Exception (SRBX) alarming.
The LOI is software-configurable with baud rates from 300 to 115.2 K
and it uses a DB9 connection.
Note:
You can purchase an LOI cable from your sales representative.
The LOI supports ROC or Modbus slave protocol communications. The
LOI also supports the log-on security feature of the FB107, if you enable
the security on LOI using ROCLINK 800.