FloBoss 107 Instruction Manual
Revised June-2017
Inputs and Outputs
4-19
SWITCHED
DEVICE
SUPPLY
POWER
DO2-DO6
LOW SIDE SWITCH
Figure 4-16. Discrete Output Relay Module Wiring (Low Side Switch)
4.12 Pulse Inputs (PI)
Pulse inputs (PI) processes signals from pulse-generating devices and
provide a calculated rate or an accumulated total over a configured
period. The FB107 pulse input circuits are physically the same as the
discrete inputs. The pulse input routes to a pulse accumulator, where the
pulses are counted and accumulated.
The PI is most commonly used to interface to open collector/open drain
type solid-state devices. Use the PI to interface to self-powered devices.
Acceptable PI voltage levels range between 0.5 volts dc (low) and 1.5
volts dc (high).
Caution
The pulse input is designed to operate with non-powered devices,
such as “dry” contacts or isolated solid-state switches. Use of the PI
with externally powered devices may cause improper operation or
damage.
Note:
Select PI as the I/O Type for the selectable pulse inputs/discrete
inputs when you configure it for use as a pulse input. Refer to
4.12.1 Wiring the Pulse Inputs
Figure 4-17
shows the terminals on the CPU module for connecting the
PI wiring. The + terminal is a positive source voltage; the GND terminal
is the signal return.
Содержание FloBoss 107
Страница 58: ...FloBoss 107 Instruction Manual 3 8 Power Connections Revised June 2017 This page is intentionally left blank ...
Страница 104: ...FloBoss 107 Instruction Manual 5 18 Communications Revised June 2017 This page is intentionally left blank ...