FloBoss 107 Instruction Manual
Revised June-2017
General Information
1-9
Default values for the LOI port are: 19,200 baud rate, 8 data bits, 1 stop
bit, no parity, group 1, and address 2.
EIA-485 (RS-485) Serial
Communications
COM1
COM1
provides EIA-485 (RS-485) serial communication protocols
with baud rates from 300 to 115.2 K
.
COM1 provides standard
differential data transmissions over distances of up to 1220 meters
(4000 feet), if wired in daisy chain pattern and properly terminated.
Note:
Using a star installation pattern reduces data transmission to 602
m (2000 ft).
The EIA-485 (RS-485) drivers are designed for true multi-point
applications with multiple devices on a single bus.
Note:
COM1 is labeled 485 on the CPU.
Use COM1 to monitor or modify the FB107 from a remote site, using a
host or ROCLINK 800. COM1 also supports the log-on security feature
of the FB107 if you enable the security on COM1 using ROCLINK 800.
COM1 sends and receives messages using the ROC or Modbus slave and
host protocol. COM1 is capable of initiating a message in support of
Spontaneous-Report-by-Exception (SRBX) alarming.
Default values for the EIA-485 (RS-485) communications are: 19,200
baud rate, 8 data bits, 1 stop bit, no parity, 10 millisecond key-on delay,
and 10 millisecond key-off delay. The maximum baud rate is 115.2 Kbps.
EIA-232 (RS-232) Serial
Communications
COM2
COM2
allows for
EIA-232 (RS-232) asynchronous serial
communication protocols with baud rates from 300 to 115.2 K, host
serial interface
.
COM2 provides standard single-ended data
transmission over distances of up to 15 meter (50 feet).
Use COM2 to monitor or alter the FB107 from a remote site, using
ROCLINK 800. COM2 also supports the log-on security feature of the
FB107 if you enable the security on COM2 using ROCLINK 800.
COM2 sends and receives messages using the ROC or Modbus slave or
host protocol. COM2 is capable of initiating a message in support of
Spontaneous-Report-by-Exception (SRBX) alarming.
Default values for the EIA-232 (RS-232) communications module are:
19,200 baud rate, 8 data bits, 1 stop bit, no parity, 10 millisecond key-on
delay, and 10 millisecond key-off delay. The maximum baud rate is 115.2
Kbps.
Note:
When you install a
communication module
in slot 2, the
firmware redirects communications port (COM2) on the CPU to
the type of module installed in slot 2. Configure COM2 based on
the type of communication module installed in slot 2.