FloBoss 107 Instruction Manual
Revised June-2017
Communications
5-3
A
LOI Local Port EIA-232 (RS-232)
B
COM1 EIA-485 (RS-485)
C
COM2 Default EIA-232 (RS-232)
Figure 5-3. CPU
The FB107 supports up to four communication ports: LOI, COM1,
COM2, and COM3:
Local Operator Interface (RS-232C)
Located on the CPU and labeled
LOI
(see
Figure 5-3
), the LOI port
provides asynchronous serial communications, with DB9 connector.
Default LOI values: 19,200 baud rate, 8 data bits, no parity, and 1
stop bit.
Note:
The LOI port located on the FB107 base unit (see
Figure 1-1
)
is factory-wired into the LOI port on the CPU. You can use
either LOI port, but
not
both.
EIA-485 (RS-485)
Located on the CPU and labeled
485
(see
Figure 5-3
), the COM1 port
provides asynchronous serial communications, and is the standard for
differential data transmission over distances of up to 1220 m (4000
ft). EIA-485 (RS-485) provides asynchronous serial communications
for multi-drop units on a serial network over long distances using
inexpensive twisted-pair cables.
Default EIA-485 (RS-485) values: 19,200 baud rate, 8 data bits, no
parity, and 1 stop bit.
A
B
C