FloBoss 107 Instruction Manual
7-10
Troubleshooting
Revised June-2017
5.
Select the configuration file you desire to restore.
6.
Click
Download
to restore the configuration.
7.4.3
Troubleshooting Analog Inputs
Before you can determine if an analog input point is operating properly,
you must first know its configuration.
configuration values for an analog input:
Table 7-1. Analog Input Module Typical Configuration Values
Parameter
Value
Value Read
Adjusted A/D 0 %
643
1
1 volt dc across the + and the COM terminal by a multimeter
Adjusted A/D 100 %
3220
1
5 Volts dc across the + and the COM terminal by a multimeter
Low Reading EU
0.0000
EU value with 1 volt dc
High Reading EU
100.0
EU value with 5 volts dc
1
The 8-channel AI/DI module has default values of 800 and 4000.
Required
Equipment
Calibration source of 1 to 5 volts dc or 4-20 mA
Multimeter
PC running ROCLINK 800 software
Caution
Failure to exercise proper electrostatic discharge precautions, such
as wearing a grounded wrist strap may reset the processor or
damage electronic components, resulting in interrupted operations.
1.
Remove the field device connected to the transmitter.
2.
Set the multimeter to measure voltage and connect it across the + and
GND terminals.
3.
Connect to ROCLINK 800.
4.
Select
Configure
>
I/O
>
AI Points
.
5.
Select the correct analog input point number.
6.
Install a voltage source of 1 to 5 volts dc and verify the following
readings:
When supplying 1 volt dc input, AI should indicate 0% EU.
When the reading goes outside the calibrated 0% and 100% A/D
counts, ROCLINK 800 indicates point fail and the input reads and
holds the last know good value or go to a user-defined value as
determined by the AI configuration.
When supplying 5 volts dc, AI should indicate 100% EU.
7.
Remove the test equipment.