Chapter 7 Troubleshooting 53
DataMate 3000 Series Air Conditioner User Manual
Chapter 7 Troubleshooting
Symptom
Possible cause
Check or remedy
No power to system
Check voltage at input terminal block
Control voltage circuit breaker (at
transformer) open
Locate short and reset circuit breaker
Float switch relay has closed due to
high water level in the condensate
pump sump
Check drain and line as well as for failed pump
Unit will not start
Jumper not in place
Check jumpers on the interface board
Compressor contactor not pulling in
Check for 24Vac
±
2Vac at terminal J74 on the
interface board. If voltage, check contactor
Compressor high head pressure
See “High pressure alarm” for cause
Plugged filter/drier
Replace filter/drier
No cooling
Low refrigerant charge
Check pressure gauges. Check if there is
evident bubbles from the sight glass
Insufficient air flow across condenser
coil
Remove debris from coil and air inlet
High pressure alarm
Condenser fan not operating
Check fan operation
Humidify function disabled
Set “Humidity” to OPEN, refer to section 5.9.2
No humidify demand from the
controller
Increase humidity control setpoint and sensitivity
to require humidification
Humidifier does not
operate
Humidity sensor failure
Humdity display will indicate dashes. Check
wiring from temperature/humidity board to the
control board
Heat function disabled
Set “Heat” to OPEN, refer to section 5.9.2
No heat demand from controller
Increase temperature setpoint to erquire heating
Heater does not
operate
Elements is burned out
Trun off power. Check element continuity with
Ohm meter
Static discharge
Disconnect the system power, and then restart
Display abnormal
Loose connection between keypad
and control board
Connection tightening after power off, and then
restart
Connection between keypad and
control board open
Check the connection between keypad and
control board
No display and
control pads do not
respond. Equipment
operates normally
Keypad failure
Replace the keypad