10 Chapter 2 Mechanical Installation
DataMate 3000 Series Air Conditioner User Manual
626
353
702
353
702
123
8
Figure 2-4 Dimensions of condenser (unit: mm)
Table 2-2 Mechanical parameters of condenser and evaporator
Evaporator
Condenser
Models
Parameters
DME07
DME12
DMC07
DMC12
Cooling capacity (kW)
7.5
12.5
Dimensions(W*D*H)(mm) 600
%
550
%
1900 600
%
550
%
1900 702
%
353
%
626 702
%
353
%
1238
Net weight (kg)
150
160
34
58
2.4 Evaporator Installation
2.4.1 Room Preparation
The room should be well insulated and must have a sealed vapor barrier. Use
polyethylene as the vapor barrier of the ceiling and the wall. Paint on concrete walls
or floors should be vapor resistant.
Note
The most important requirement for maintaining environmental control in the conditioned
room is the vapor barrier.
Incoming fresh air should be kept to a minimum. Incoming outside air adds to the
heating, cooling, humidifying loads of the site. It is recommended that outside air be
kept below 5% of the total circulated in the room. Doors and windows should be
properly sealed to minimize leaks.