Chapter 4 System Commission 29
DataMate 3000 Series Air Conditioner User Manual
4.3.3 Humidification Operation
According to section 5.7, set the humidification setpoint to 10% higher than the
room relative humidity. The controller should send a humidification command, and
the canister humidifier is activated. Set the setpoint to be lower than the room
relative humidity. If the humidifier is deactivated, humidification operation is normal.
Note
Change the setpoint to the default or the original point after the test.
4.3.4 Dehumidification Operation
According to section 5.7, set the humidification setpoint to 10% lower than the room
relative humidity. The controller should send a dehumidification command, and the
blower runs at low speed. Set the setpoint to be higher than the room relative
humidity. If the blower runs at high speed, dehumidification operation is normal.
During this progress, pay attention that if the room temperature is 3°C higher than
the setpoint, dehumidification requirement may not be responded, as the system
may operate under the forced cooling mode.
Note
Change the setpoint to the default or the original point after the test.
Read next chapter to configure relevant parameters when system operates
normally after the test.