4 Chapter 1 Introduction
DataMate 3000 Series Air Conditioner User Manual
1.4 Main Parts
1.4.1 Evaporator Module
The evaporator module consists of an evaporator, a compressor, a heater (optional),
blower, controller, humidifier (optional), thermal expansion valve, sight glass and
filter dryer.
1.4.2 Condensing Module
The condensing module consists of a fan, a condenser and a fan motor.
1.4.3 Pressure Switch
High and low pressure switches are used to protect the refrigerant system. The
action point of the high pressure switch is 2.76MPa and the recovery point is
2.1MPa. The action point of the low pressure switch is 0.12MPa, and the recovery
point is 0.25MPa.
1.4.4 Blower Speed Controller
The controller regulates the air volume of the blower automatically according to the
condensate pressure of the system to maintain a favorable temperature. Thus the
compressor can work normally even if the outdoor temperature is very low.
1.5 Optional Parts
1.5.1 Humidifier
It adds pure water vapor (up to 2kg/hour) to the room air to control humidity within
the levels recommended for computer system.
The humidifier components include the steam canister with automatic flushing
circuit, inlet tube, drain, solenoid valve, and steam distributor.
Note
1. The electric humidifier should be factory installed and tested.
2. Humidity control is available only if a humidifier is provided.