Chapter 1 Introduction 3
DataMate 3000 Series Air Conditioner User Manual
1.2.3 Condenser
The condenser includes a high efficiency fin-tube heat exchanger. The blower
includes a low noise propeller fan driven by a high performance single-phase motor.
The motor is customized to adapt to the power network of base stations, so it can
work over a wide voltage range with a high reliability.
1.3 Environment Requirement
1.3.1 Operating Environment
Refer to Table 1-1 for detailed operating environmental requirements.
Table 1-1 Operating environmental requirements of DataMate3000 system
Item
Requirement
Installation position
The max. equivalent horizontal distance of the
evaporator and condensing modules: 50m;
Altitude distance* H: -5m
≤
H
≤
20m
Installation method
Vertical
Environmental temperature
Indoor: 0°C~30°C; Outdoor: -15°C~45°C
Relative humidity
30%~80%RH
Protection level (Condensing module)
IPX4
Altitude <1000m
Range of operation voltage
380V±25%
*: A negative altitude distance means that the condenser is mounted below the
compressor.
1.3.2 Storage Environment
Refer to Table 1-2 for detailed storage environmental requirements.
Table 1-2 Storage enriromental requirements of DataMate3000 system
Item
Requirement
Storage environment
Indoor, without dust
Relative humidity
5%~95%RH
Environmental
temperature
-40°C~70°C
Storage time
The shipment and storage time should not exceed 12 months.
Otherwise, the system shall be re-tested