Chapter 2 Mechanical Installation 7
DataMate 3000 Series Air Conditioner User Manual
2.3 System Installation Arrangement
2.3.1 General Arrangement
The system general arrangement diagram is shown in Figure 2-1. The
recommended line size is shown in Table 2-1.
Condenser
coil
Check
valve*
Traps* every 6m of
vertical lift
Discharge
line
Liquid
line
Female quick
connect coupling
Male quick
connect coupling
Solenoid valve+
Filter
drier
Sight
glass
Suction line
Sensing bulb
Scroll compressor
Distributor/
Feeder tubes
Evaporator
coil
Thermal
expansion
valve
Valve core
Valve core
Figure 2-1 DataMate3000 general arrangement diagram
Factory piping
Field piping (by others)
* Check valve and traps are optional and not supplied by Emerson. But they are
recommended for field installation for proper circuit operation and maintenance.
They should be installed on site by technical personnel.
+ Solenoid valve is part of optional extended piping kit.
Table 2-1 Recommended line size
Actual capacity
Length Discharge line O.D Liquid line O.D
7.5kW (6500 calories; 2.2 tons)
10m
1/2” (12.7mm)
3/8” (9.52mm)
12.5kW (10800 calories; 3.6 tons)
10m
5/8” (15.88mm)
1/2” (12.7mm)