8 Chapter 2 Mechanical Installation
DataMate 3000 Series Air Conditioner User Manual
2.3.2 System Installation Illustration
The evaporator and condenser must stand on the floor or ground. The
DataMate3000 can be installed in two ways. One is to install the condenser higher
than the evaporator and the other is to install the condenser lower than the
evaporator, as shown in Figure 2-2.
Condenser
Liquid line (not be
exposed to sun)
Trap
Evaporator
Protection
tube
1:200
Discharge
line(slope)
Insulation floor
Humidifier water
supplyline
(from
water supply tube)
1:200
Drain line (trapped
outside room)
Floor
Insulation
material
Seal and
vapor seal
Max. 20
m
6m
(a) Condenser higher than evaporator
Liquid line (not be
exposed to sun)
Seal and
vapor seal
Condenser
Max. 5
m
Insulation material
Floor
1:200
Drain line (trapped
outside the room)
Insulation floor
1:200
Discharge
line (slope)
Protection tube
Evaporator
Humidifier water
supply line (from
water supply tube)
(b) Condenser lower than evaporator
Figure 2-2 DataMate3000 installation illustration