2.5 Condenser Installation
2.5.1 Location Considerations
1. The condenser should be located for maintenance accessibility and away from
residential areas. Avoid ground-level sites with public access.
2. Do no locate the condenser directly in the environment that requires low noise.
3. To ensure a satisfactory air supply, locate the condenser in a clean area, away
from loose dirt and foreign matter that may clog the heat exchanger.
4. Do not locate the condenser in the vicinity of steam, hot air, or fume exhausts.
5. Do not locate the condenser closer than 450mm from a wall, obstruction or
adjacent unit.
6. Avoid areas where heavy snow will accumulate at air inlet and discharge
locations.
7. Install a solid base capable of supporting the weight of the condenser. The base
should be at least 50mm higher than the surrounding ground and 50mm larger than
the dimensions of the condenser base, as shown in Figure 2-9.
2.5.2
Installation Procedure
1. Uncrate the condenser and place it onto the base.
2. Secure the condenser with expansive bolts. The installation sizes are shown in
Figure 2-8.
712
374
394
617
R6
Figure 2-8 Condenser installation dimensions (unit: mm)
3. If multiple condensers are installed up and down, refer to Figure 2-9.