210-10 ADL
23/62
599 75 60-77
When Tpreset
<
Tamb.
<
Tpreset
+
3
℃
, indoor fan operates at medium speed;
When Tpreset-2
<
Tamb.≤Tpreset, indoor fan operates at low fan speed;
When Tamb. ≤Tpreset-2
℃
, indoor fan operates at quiet mode.
③
Auto fan speed is not available in drying mode
Note: high speed, medium speed and low speed is to “notch 5”, “notch “3” and “notch 1” respectively.
As for the switchover among high speed, medium speed and low speed, the unit should operates at every speed for 3minutes
and 3s at least.
(8) Control of Up&Down Swing
a. Small Horizontal Louver
After energization, small swing motor will firstly have the horizontal louver rotate anticlockwise to position 0 to close air outlet.
If swing function has not been set after startup of the unit, horizontal louver will turn clockwise to position D1 in HEAT mode. If
swing function is set when starting up the unit, the horizontal louver will swing between 0and D1.
There are 7 swing status of horizontal louver: Positions O, A1, B1, C1, D1, swing between O and D1 and stop at any position
between O and D1 (angles between O and D1 are equiangular mostly). In other statues, horizontal louver will close at position
O.
Upon turning off the unit, the horizontal louver will close at position 0.
Swing is valid only when swing command is set and indoor fan operates.
Note:1. If the position is set between O and D1, A1 and C1 or B1 and D1 by remote controller, the horizontal louver will swing
between O and D1.
2. As for 9k/12k, only when the big horizontal louver rotates to he second swing angle position in heating (corresponding angle
is 62º), the horizontal louver will start action. As for 18k, only when the big horizontal
louver rotates to the first swing angle position in heating (corresponding angle is 64 º),
the horizontal louver will start action. As for 24k, only when the
big horizontal louver rotates to the first swing angle position
in heating (corresponding angle is 40 º), the horizontal louver start action.
3. In cooling mode, the horizontal louver stops at position O all the time.
b. Big Horizontal Louver
After energization, up & down swing motor will firstly have the horizontal louver rotate anticlockwise to position 0 to close air
outlet.
If swing function has not been set after startup of the unit, horizontal louver will turn clockwise to position D in HEAT mode, or
turn clockwise to level position L in other modes.
If swing function is set when starting up the unit, the horizontal louver will swing between L and D.
There are 7 swing status of horizontal louver: Positions L, A, B, C and D,
swing between L and D and stop at any position between L and D
(angles between L and D are equiangular).
Upon turning off the unit, the horizontal louver will close at position 0.
Note:1) If the position is set between L and B, A and C or B and D by
remote controller, the horizontal louver will swing between L and D.
Содержание EXH09HL1W
Страница 2: ...2010 10 ADL 2 62 599 73 60 74 ...
Страница 5: ...210 10 ADL 5 62 599 75 60 77 2 ESD Requirements ...
Страница 6: ...210 10 ADL 6 62 599 75 60 77 ...
Страница 13: ...210 10 ADL 13 62 599 75 60 77 EXH09HL1W outdoor EXH12HL1W outdoor ...
Страница 28: ...210 10 ADL 28 62 599 75 60 77 BOTTOM VIEW ...
Страница 37: ...210 10 ADL 37 62 599 75 60 77 H6 Malfunction Flowchart ...