3.2 Each Troubleshooting and Schematic Diagram
3.2.1 Firstly, check if power supply is normal
Check if power supply is normal and the voltage is between 165V~235V.
3.2.2 Refer to
Malfunction Code Table
and confirm the malfunction according to malfunction code displayed on indoor
unit.
F1,F2 Malfunctions
Malfunction of indoor ambient temperature sensor: F1 is displayed; COOL LED lamp is off for 3s and blinks once; (That the LED
lamp is on for 0.5s and off for 0.5s is a blink.)
Malfunction of indoor pipe temperature sensor: F2 is displayed; COOL LED lamp is off for 3s and blinks twice; (That the LED
lamp is on for 0.5s and off for 0.5s is a blink.)
Resistance of indoor ambient temperature sensor: 15KΩ
Resistance of indoor pipe temperature sensor: 20KΩ
Reference voltage value of temperature sensor: 0VDC
Diagram of Interfaces of Temperature Sensors:
Indoor tube temp.
sensor
Temp. sensor
reference
voltage spot
Indoor ambient
temp. sensor