Gateway configuration manual 

 

 

Profinet Slave/KNX TP – EK-BN1-TP  

 

 

Revision 1.0.2 - Update: 10/12/2018 

 

Configuration manual 

© EKINEX S.p.A. – All rights reserved 

 

Page 18 

Field name 

Values 

Description 

ReTest 

checked 

/ unchecked

 

Enables the re-send of a frame in case of wrong response message 

OnCMD 

checked 

/ unchecked

 

Not used 

OnChange 

checked 

/ unchecked

 

Event which enables the automatic sending of command frames over the 

KNX bus when the data on the Profinet device changes their values. 

OnTimer 

checked 

/ unchecked

 

Event which enables the cyclical sending of command frames over the 

KNX bus. 

Poll Time 

 

Cyclic poll time (in ms) when OnTimer event is enabled. 

Position 

Value in range [0…1439] 

Position of the first byte where a data is stored, in the internal support 

memory buffer. In case of a record where APCI=read, 

Position

  refers to 

the “KNX image” buffer; in case of APCI=write, 

Position

  refers to the 

“Profinet image” buffer. 
Please refer to  the paragraph concerning the structure of the memory 

image to perform  a correct addressing  and avoid overlaps  between the 

two data buffers. 

Bit Mode 

No / 0 / 1 / 2 / 3 /  

4 / 5 / 6 / 7 

Position, inside the first byte of the internal support memory buffer, where 

a 1-bit data is stored. 

Lenght 

 

Size (in number of bytes) of the data stored inside the internal memory. 

Mnemonic 

 

Text to comment the record and/or the datapoint over the KNX bus. 

 

 

If 

OnChange 

field is selected, 

OnTimer

 in selected and 

Poll Time 

≠ 0, the gateway will 

send the commands both cyclically and on change of the data acquired over the Profinet 

network. 
If 

OnChange

  and 

OnTimer 

fields are not selected, the gateway will only store the 

communication objects exchanged through the multicast frames over the KNX network 

(“sniffer” function). 

 
Conversion types of internal data selectable through 

Format

 field: 

Conversion 

APCI = read 

APCI = write 

None 

The value of the communication object is 

transferred in raw mode to the “KNX 

image” buffer and sent as register to the 

Profinet network. 

The value of the communication object 

acquired over the Profinet network and 

stored in the “Profinet image” buffer is 

transferred in raw mode as communication 

object over the KNX network. 

Swap16 

16-bit swap inside the stored data 

16-bit swap inside the stored data 

Swap32 

32-bit swap inside the stored data 

32-bit swap inside the stored data 

Swap All 

All bit swap inside the stored data 

All bit swap inside the stored data 

Int to Float 

 

The integer value acquired over the 

Profinet network is converted to a 2-byte 

(DPT 9.xxx) floating point value in order to 

be sent as communication object over the 

KNX network. 

Float to Int 

The 2-byte (DPT 9.xxx) floating point 

communication object value is converted 

to integer. 

 

Float 16 to Float 32 

The 2-byte (DPT 9.xxx) floating point 

communication object value is converted 

to a 32-bit floating point value (according 

to standard IEEE 754). 

 

 

 

 

 

Содержание EK-BN1-TP

Страница 1: ...Gateway configuration manual PROFINET Slave KNX TP EK BN1 TP...

Страница 2: ...play and connection elements 6 3 Configuration and commissioning 8 4 Profinet protocol general information 9 4 1 Tecnology 9 4 2 Profinet CBA 9 4 3 Profinet IO 9 4 4 Addressing 9 4 5 Real time RT 10 4...

Страница 3: ...ve The informations exchanged over the Profinet network are updated over the KNX network by means of a twisted pair TP communication cable The device manages a two way data stream the Profinet registe...

Страница 4: ...alues of the acquired communication objects are stored in a 1440 byte volatile memory buffer KNX image memory This buffer is independent from the Profinet image memory buffer Profinet network Register...

Страница 5: ...e Configuration and commissioning of the ekinex gateway must be performed using the application program CGEKBN1TP available for download at www ekinex com The PC where the application program is insta...

Страница 6: ...rk connection and device configuration via Ethernet as well as one 1 way microswitches are also present Figure 1 Switching display and connection elements 1 KNX bus line terminal blocks 2 KNX programm...

Страница 7: ...linking 0 5 Hz loading configuration Yellow LED 10 KNX communication Blinks when a frame is received Fast blinking no configuration Very slow blinking 0 5 Hz loading configuration Yellow LED 11 Device...

Страница 8: ...rt delays CGEKBN1TP application software to properly configure the gateway Knowledge of the ETS automation project with particular attention to communication objects and group addresses passing on the...

Страница 9: ...rresponding outputs which are then sent to another controller 4 3 Profinet IO The peripheral interfacing is implemented by Profinet IO protocol Profinet IO defines the whole data exchange between mast...

Страница 10: ...e base for Profinet IO data exchange Real time data are treated with a greater priority than TCP IP or UDP IP data this kind of data exchange allows to achieve cycle times inferior to 1ms 4 6 Isochron...

Страница 11: ...inet network creation of GSD file to import in master s configuration Firmware and or configuration update The application program consists in multiple modal windows called forms each form must be clo...

Страница 12: ...ytes Each support byte can be individually addressed see Position field in KNX Set Access form or you can target a specific support bit in each buffer Bit Mode field in KNX Set Access form As shown in...

Страница 13: ...configuration files are stored on the hard drive in XML format Figure 5 Create new configuration form Figure 6 Create new configuration form In order to duplicate an existing project you must find th...

Страница 14: ...BN1 TP Revision 1 0 2 Update 10 12 2018 Configuration manual EKINEX S p A All rights reserved Page 14 5 3 Software Options The Software Options form allows you to select a different language for the a...

Страница 15: ...ameter identifies the physical address assigned to the KNX device The format requires the use of a dot as a separator beween the 3 fields area line and device address Here are the conventions used for...

Страница 16: ...2 Update 10 12 2018 Configuration manual EKINEX S p A All rights reserved Page 16 Parameter name Values Description PROFINET Name of Station Profinet device name Number Byte IN Number of input bytes...

Страница 17: ...s as a filter Through this field you can acquire datapoints of all lines over the KNX bus 0 0 0 value or you can select one specific line e g 4 3 0 or a single device identified by a specific physical...

Страница 18: ...r the datapoint over the KNX bus If OnChange field is selected OnTimer in selected and Poll Time 0 the gateway will send the commands both cyclically and on change of the data acquired over the Profin...

Страница 19: ...Profinet registers configuration By pressing Profinet XML button you can access to the form that creates the GSD XML file which contains the information about the data to be exchanged between the Prof...

Страница 20: ...1 way microswitch A see Figure 1 Switching display and connection elements to ON position Power on the device Connect PC and device by means of an Ethernet cable Make sure that the PC s network parame...

Страница 21: ...rrectly applied the procedure the text Device found will appear see Figure 12 Update configuration form Press Next button see Figure 12 Update configuration form Select the desired options see Figure...

Страница 22: ...run the program using the primary OS When using Windows 7 or later make sure the user has administrator privileges Pay attention to firewall settings Check LAN configuration In case of manual firmware...

Страница 23: ...nex KNX defective devices must be returned to the manufacturer at the following address EKINEX S p A Via Novara 37 I 28010 Vaprio d Agogna NO Italy 7 Other information This application manual is aimed...

Отзывы: