Gateway configuration manual 

 

 

Profinet Slave/KNX TP – EK-BN1-TP  

 

 

Revision 1.0.2 - Update: 10/12/2018 

 

Configuration manual 

© EKINEX S.p.A. – All rights reserved 

 

Page 15 

5.4  Communication parameters 

In this section we define the basic communication parameters for the KNX TP network and for Ethernet 

connection. Ethernet connection is required in order to both perform the configuration update on the device 

and for Profinet communication. 
 

 

Figure 8 – Set communication form 

 
You can access the form by pressing the 

Set Communication 

button in the main form (see Figure 2 – Main 

form of the application program). 
 
Description of fields in 

Set communication

 form. 

Parameter name 

Values 

Description 

KNX 

Type 

KNX TP 

Type of connection used for KNX communication. The parameter has a 

constant value “KNX TP”. The device supports KNX communicaton over a 

twisted pair communication cable. 

ID Device 

 

This parameter identifies the physical address assigned to the KNX device. 

The format requires the use of a dot “.” as a separator beween the 3 fields: 

area, line and device address. Here are the conventions used for physical 

addressing and the values used for each field: 
Area field: = 0 reserved for backbone, values [1...15] 
Line field: = 0 reserved for main line, values [1...15] 
Device address field: = 0 reserved for coupler, values [1...255], range [1..64] 

for devices belonging to the line, above 64 for device belonging to extensions 

or other segments of the line. 
Example: 1.3.5: Area = 1; Line = 3; Device address = 5. 

PROFINET 

IP ADDRESS 

 

IP Address (4-octet format) assigned to the device. Each octet is set in an Edit 

box. Default IP Address is: 

192.168.2.205

. This is the address assigned to the 

device before the first configuration or after a complete restore. 

SUBNET Mask 

 

Subnet mask assigned to the device. 

GATEWAY 

 

Gateway address used  for Ethernet communication. The gateway can be 

enabled or disabled through the control check-box placed at the right side of 

the field. 

Port 

34964 

Port used for Profinet communication 

Содержание EK-BN1-TP

Страница 1: ...Gateway configuration manual PROFINET Slave KNX TP EK BN1 TP...

Страница 2: ...play and connection elements 6 3 Configuration and commissioning 8 4 Profinet protocol general information 9 4 1 Tecnology 9 4 2 Profinet CBA 9 4 3 Profinet IO 9 4 4 Addressing 9 4 5 Real time RT 10 4...

Страница 3: ...ve The informations exchanged over the Profinet network are updated over the KNX network by means of a twisted pair TP communication cable The device manages a two way data stream the Profinet registe...

Страница 4: ...alues of the acquired communication objects are stored in a 1440 byte volatile memory buffer KNX image memory This buffer is independent from the Profinet image memory buffer Profinet network Register...

Страница 5: ...e Configuration and commissioning of the ekinex gateway must be performed using the application program CGEKBN1TP available for download at www ekinex com The PC where the application program is insta...

Страница 6: ...rk connection and device configuration via Ethernet as well as one 1 way microswitches are also present Figure 1 Switching display and connection elements 1 KNX bus line terminal blocks 2 KNX programm...

Страница 7: ...linking 0 5 Hz loading configuration Yellow LED 10 KNX communication Blinks when a frame is received Fast blinking no configuration Very slow blinking 0 5 Hz loading configuration Yellow LED 11 Device...

Страница 8: ...rt delays CGEKBN1TP application software to properly configure the gateway Knowledge of the ETS automation project with particular attention to communication objects and group addresses passing on the...

Страница 9: ...rresponding outputs which are then sent to another controller 4 3 Profinet IO The peripheral interfacing is implemented by Profinet IO protocol Profinet IO defines the whole data exchange between mast...

Страница 10: ...e base for Profinet IO data exchange Real time data are treated with a greater priority than TCP IP or UDP IP data this kind of data exchange allows to achieve cycle times inferior to 1ms 4 6 Isochron...

Страница 11: ...inet network creation of GSD file to import in master s configuration Firmware and or configuration update The application program consists in multiple modal windows called forms each form must be clo...

Страница 12: ...ytes Each support byte can be individually addressed see Position field in KNX Set Access form or you can target a specific support bit in each buffer Bit Mode field in KNX Set Access form As shown in...

Страница 13: ...configuration files are stored on the hard drive in XML format Figure 5 Create new configuration form Figure 6 Create new configuration form In order to duplicate an existing project you must find th...

Страница 14: ...BN1 TP Revision 1 0 2 Update 10 12 2018 Configuration manual EKINEX S p A All rights reserved Page 14 5 3 Software Options The Software Options form allows you to select a different language for the a...

Страница 15: ...ameter identifies the physical address assigned to the KNX device The format requires the use of a dot as a separator beween the 3 fields area line and device address Here are the conventions used for...

Страница 16: ...2 Update 10 12 2018 Configuration manual EKINEX S p A All rights reserved Page 16 Parameter name Values Description PROFINET Name of Station Profinet device name Number Byte IN Number of input bytes...

Страница 17: ...s as a filter Through this field you can acquire datapoints of all lines over the KNX bus 0 0 0 value or you can select one specific line e g 4 3 0 or a single device identified by a specific physical...

Страница 18: ...r the datapoint over the KNX bus If OnChange field is selected OnTimer in selected and Poll Time 0 the gateway will send the commands both cyclically and on change of the data acquired over the Profin...

Страница 19: ...Profinet registers configuration By pressing Profinet XML button you can access to the form that creates the GSD XML file which contains the information about the data to be exchanged between the Prof...

Страница 20: ...1 way microswitch A see Figure 1 Switching display and connection elements to ON position Power on the device Connect PC and device by means of an Ethernet cable Make sure that the PC s network parame...

Страница 21: ...rrectly applied the procedure the text Device found will appear see Figure 12 Update configuration form Press Next button see Figure 12 Update configuration form Select the desired options see Figure...

Страница 22: ...run the program using the primary OS When using Windows 7 or later make sure the user has administrator privileges Pay attention to firewall settings Check LAN configuration In case of manual firmware...

Страница 23: ...nex KNX defective devices must be returned to the manufacturer at the following address EKINEX S p A Via Novara 37 I 28010 Vaprio d Agogna NO Italy 7 Other information This application manual is aimed...

Отзывы: