KGL Operating Manual – UA 412 S
2019-01-14
/
97 122
Menu 6-3 Cooling
KÜHLUNG POS:
XXXXX
Input
Default
min. Laufzeit XX K
Minimum run time of the cooling
0..15
5 m
min. Standzeit XX m
Minimum switch-off time of the cooling
0..15
5 m
Dauerl.überw. XX m
Time for the forced interruption of the cooling during continuous operation
--, 0..
15
7 m
Notbetrieb XX m
If necessary sensors for the regulation fail, the solenoid valve is actuated with the opening degree in
[%]set here.
0..100
40%
Menu 6-4 - Language
SPRACHEPOS: XXXXX
Input
Default
Deutsch D
English GB
Français F
Menu 6-5 Alarm priorities
ALARMPRIOSPOS: XXXXX
Input
Default
Kühlstellenprio X
Priority of the alarms can be set
globally using the refrigeration point
priority (menu 6-1) (Y)
,
,
(Y,
N)
N
Priority: XX
Display of refrigeration point priority
(menu 6-1)
only displayed if Kühlstellenprio is set
to Y
The following priorities are only displayed ig Kuhlstellenprio is set to N. The possible
entries for the priority of the alarms have the following meanings:
-=Event is ignored
0=Message (only entry in message list) 1=Alarm with priority 1 .. 99=Alarm with
priority 99
Low temp.
Lower alarm temperature limit value
undercut; priority is applicable for all
messages
low-temp. zone 1, low-temp.
zone 2
-, 0..
99
0
High temp
Upper alarm temperature limit value
exceeded; priority is applicable for all
messages
high-temp. zone 1, high-
temp. zone 2
-, 0..
99
1
Sensor fault
Temperature sensor failed
-, 0..
99
0
No Defrost
No defrost within the alarm delay time
Priority is applicable for the message
No Defrost
-, 0..
99
0
Timer-Term. Defrost
Defrost ended by safe defrost time
-, 0..
99
0
Power failure
Start-up after power failure
-, 0..
99
0
First start
0