KGL Operating Manual – UA 412 S
2019-01-14
/
50 122
4. Exit from the menu
by tapping the
button once and select menu
1 Refrigeration point
ESC
6 Configuration -
.
2 Controller
6 Configuration - 2 Controller
REGLERPOS: XXX
1 Type and version
Type, serial number and Master / Slave (ON/OFF)
2 Temperature display
Adjustment of the displayed temperature value
3 Alarm delay
Input of an alarm delay time
4 230 V inputs
230 V inputs
5 Sensor type
Selection of the temperature sensor of the type L243, K277 or 5K3A1
5. Select menu
-
.
6 Configuration - 2 Controller 3 Alarm delay
6 Configuration – 2 Controller – 3 Alarm delay.
ALARMVERZ.POS: XXX
Fühlerbruch XXm
Alarm delay for sensor fault
Über/Unter Tmp XXXm
Alarm delay for high temperature or low temperature
keine Abtauung XXXh
Alarm is tripped if no defrost is performed within this configurable time.
Selbsthaltung N
NO: Automatic reset of non-transient alarms
YES: Alarms must be reset manually
Exit the menu by tapping the
button once.
ESC
6. Exit the
menu by tapping the
button twice and select
Configuration
ESC
3 Clock – 2 Defrost timer
Input of the relevant parameters in the following screen.
3 Clock - 2 Defrost Timer
ABTAUUHRPOS: XXX
Defrost timer INT
Selection of defrost using external or internal defrost timer
Sicherheitsz. 60 min
Safe defrost time; the defrost is not longer than this time.
Defrost 1 DD-DD hh:mm
Entry of defrost times
Defrost 2 DD-DD hh:mm
...
Defrost 14 DD-DD hh:mm
man. AbtauungAUS
Manual defrost ON/OFF
8. Exit from the
menu by tapping the
button.
2 Defrost Timer
ESC
9. Select menu
, input of the relevant parameters in the following screen:
3 Toggle Setpoint
3 Clock - 3 Toggle Setpoint
UMSCHALTNGPOS: XXX
Status AUS
Only visible if Sollumschaltg. is set to INT or EXT